| Plan Review Notes For Permit 04040676 |
| Permit Number |
04040676 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-23 00:00:00 | DENIED: | | | TRANSFER GRILLE FROM THE MASTER BEDROOM | | | IS NOT SIZED PROPERLY.PER THE REVISED | | | 2001 FBC(M) 601.4 EXCEPTION #2 & 3, | | | TRANSFER GRILLES SHALL BE A MINIMUM OF | | | 50 SQ IN PER 100 CFM.ALL SUPPLY AIR | | | INTO THE MASTER SUITE IS TO BE INCLUDED | | | FOR THE TOTAL OF SUPPLY AIR TO THE | | | SUITE.PLEASE SIZE TRANSFER GRILL | | | ACCORDINGLY. | | | | | | AUXILIARY DRAIN PAN REQUIRED PER 2001 | | | FBC(M) 307.2.3. | | | | | | CONDENSATE SHALL TERMINATE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE PER | | | 2001 FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|