2004-04-23 00:00:00DENIED:
 TRANSFER GRILLE FROM THE MASTER BEDROOM
 IS NOT SIZED PROPERLY.PER THE REVISED
 2001 FBC(M) 601.4 EXCEPTION #2 & 3,
 TRANSFER GRILLES SHALL BE A MINIMUM OF
 50 SQ IN PER 100 CFM.ALL SUPPLY AIR
 INTO THE MASTER SUITE IS TO BE INCLUDED
 FOR THE TOTAL OF SUPPLY AIR TO THE
 SUITE.PLEASE SIZE TRANSFER GRILL
 ACCORDINGLY.
  
 AUXILIARY DRAIN PAN REQUIRED PER 2001
 FBC(M) 307.2.3.
  
 CONDENSATE SHALL TERMINATE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE PER
 2001 FBC 1503.4.4.
  