2004-04-17 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 SHOWN FOR PANEL, NEED FOR MAIN DISC.
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISC TO
 PANEL. 250.110,250.24, SIZE PER 250.122
  
 3)NOTE: PLEASE SEE OCP FOR AHU 5W.
 PLEASE CORRELATE WITH MECH PLANS.
 PLEASE ALSO VERIFY MAX OCP FOR 5KW UNIT.
 PLEASE SEE POSSIBLE MECH COMMENTS FOR
 5KW HEAT FOR A HOUSE OF THIS SQ FT.
  
 4) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  