| Plan Review Notes For Permit 04040676 |
| Permit Number |
04040676 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-17 00:00:00 | *********** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | SHOWN FOR PANEL, NEED FOR MAIN DISC. | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN DISC TO | | | PANEL. 250.110,250.24, SIZE PER 250.122 | | | | | | 3)NOTE: PLEASE SEE OCP FOR AHU 5W. | | | PLEASE CORRELATE WITH MECH PLANS. | | | PLEASE ALSO VERIFY MAX OCP FOR 5KW UNIT. | | | PLEASE SEE POSSIBLE MECH COMMENTS FOR | | | 5KW HEAT FOR A HOUSE OF THIS SQ FT. | | | | | | 4) NOTE: PLEASE LIST ALL THE REQ'D | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.52D, 210.11C3 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|