Plan Review Notes
Plan Review Notes For Permit 04040671
Permit Number 04040671
Review Stop E
Sequence Number 2
Notes
Date Text
2004-05-28 00:00:00**************** UNSAT ***********
  
 1)NOTE: PLEASE SEE SHUNT TRIP MAY NOT
 BE USED AS THE MEANS OF DISCONNECT
 GROUPED WITH EXISTING.
 PLEASE SEE GROUPING OF MAINS, 230.72,
 RATING OF DISCONNECT AND MANUALS MEANS
 230.76,230.79. ETC.
  
 2)NOTE: PLEASE INDICATE FULL LOAD FOR
 SERVICE. EXISTING SEC'S ARE RATED FOR
 400A'S. PLEASE VERIFY LOAD FOR NEW
 AND EXSITING.
  
 3)NOTE: PLEASE SEE CHAPTER 34FBC
 3401.7.1.2.1PLEASE VERIFY EITHER
 EXISTING OR NEW SD'S TO CURRENT CODE
 AND ALL GFI'S REQ'D PER 2002 NEC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  