Plan Review Notes
Plan Review Notes For Permit 04040671
Permit Number 04040671
Review Stop B
Sequence Number 2
Notes
Date Text
2004-06-09 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR
 THE IMPACT FEES.
  
 2) THE STATE PRODUCT APPROVAL THAT WAS
 SUBMITTED FOR THE SKYLIGHTS IS FOR A
 SUNDOME AND NOT FOR THE 2'X 4' SKYLIGHTS
 THAT ARE SHOWN ON THE PLANS. PLEASE
 REVISE PLANS OR SUBMIT CORRECT PRODUCT
 APPROVAL.
  
 3) THE PRODUCT APPROVALS SUBMITTED FOR
 THE OVERHEAD GARAGE DOORS DO NOT HAVE
 DESIGN PRESSURES THAT MEET THE REQUIRE-
 MENTS OF THE PLANS.
  
 4) AN H10 CONNECTOR (WOOD TO WOOD) IS
 SEPCIFIED FOR A SECTION OF THE
 CONNECTING HALL THAT HAS A CONCRETE TIE
 BEAM. PLEASE SPECIFY AN APPROPIATE
 CONNECTOR (WOOD TO CONCRETE) FOR THIS
 AREA. SEE NOTES ON SHEET A7 OF PLANS.
  
 5) A SEPARATE PERMIT WILL BE REQUIRED
 FOR ROOFING.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714