2004-05-10 00:00:00DENIED:
 MECHANICAL PLAN INDICATES AHU #2
 SERVINGTHE GARAGE, AIR FROM THE GARAGE
 AREA SHALL NOT BE RECIRULATED, OUTSIDE
 AIR REQUIRED AT A RATE OF 100 CFN PER
 VEHICLE, PER 2001 FBC(M) TABLE 403.3.
  
 UNITS FOR DE-HUMIDIFACATION PUPOSES
 SHALL BE CONTROLLED BY A HUMIDISTAT PER
 2001 FBC CHAPTER 13 607.1.ABC.2.3.
  