Plan Review Notes
Plan Review Notes For Permit 04040671
Permit Number 04040671
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-08 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE INCLUDE ARCH'S CA# ON
 TITLE BLOCK AS REQ'D UNDER FS 481.219
 FAC 61G1-16.004.
 THIS IS REQ'D ON ALL SHEETS AND FOR ALL
 TRADES SHEETS, WEATHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWERS.
  
 2)NOTE: PLEASE SEE THAT CHANGES MADE
 TO PLANS W/ BLACK MARKER ARE NOT PERMIT-
 -TED TO SIGNED AND SEALED PLANS.
  
 3)NOTE: PLEASE CLARIFY IF NEW MAIN IS
 GROUPED WITH THE OTHER TWO MCB PANELS
 PER 230.72
  
 4)NOTE: PLEASE PROVIDE LOAD COMPLETE
 LOAD CALCULATIONS FOR SERVICE SHOWING
 NEW AND EXISTING.
  
 5)NOTE: PLEASE SEE 210.12 2002 NEC,
 PLEASE LIST THE REQ'D ARC FAULT CIRCUIT(
 S).
  
 6)NOTE: PLEASE SEE OCP FOR AHU'S .
 SHOWS 60A OCP FOR 5KW HEAT>
 424.3B.
  
 7)NOTE: PLEASE VERIFY ANY REQ'MENTS FOR
 CHAPTER 34 FBC.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE SUBMITT-
 -ED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2004-05-07 00:00:00************** UNSAT *************
  
 NOTES TO FOLLOW.