| 2004-05-08 00:00:00 | ************* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE INCLUDE ARCH'S CA# ON |
| | TITLE BLOCK AS REQ'D UNDER FS 481.219 |
| | FAC 61G1-16.004. |
| | THIS IS REQ'D ON ALL SHEETS AND FOR ALL |
| | TRADES SHEETS, WEATHER OR NOT COMMENT |
| | IS MADE BY OTHER REVIEWERS. |
| | |
| | 2)NOTE: PLEASE SEE THAT CHANGES MADE |
| | TO PLANS W/ BLACK MARKER ARE NOT PERMIT- |
| | -TED TO SIGNED AND SEALED PLANS. |
| | |
| | 3)NOTE: PLEASE CLARIFY IF NEW MAIN IS |
| | GROUPED WITH THE OTHER TWO MCB PANELS |
| | PER 230.72 |
| | |
| | 4)NOTE: PLEASE PROVIDE LOAD COMPLETE |
| | LOAD CALCULATIONS FOR SERVICE SHOWING |
| | NEW AND EXISTING. |
| | |
| | 5)NOTE: PLEASE SEE 210.12 2002 NEC, |
| | PLEASE LIST THE REQ'D ARC FAULT CIRCUIT( |
| | S). |
| | |
| | 6)NOTE: PLEASE SEE OCP FOR AHU'S . |
| | SHOWS 60A OCP FOR 5KW HEAT> |
| | 424.3B. |
| | |
| | 7)NOTE: PLEASE VERIFY ANY REQ'MENTS FOR |
| | CHAPTER 34 FBC. |
| | |
| | PLEASE REMOVE ALL OLD VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO TWO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS SHOULD BE SUBMITT- |
| | -ED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |