Plan Review Notes
Plan Review Notes For Permit 04040671
Permit Number 04040671
Review Stop B
Sequence Number 1
Notes
Date Text
2004-05-12 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. THE IMPROVEMENT
 DESCRIBED IN THE NOTICE OF COMMENCEMENT
 MUST ACTUALLY COMMENCE WITHIN 90 DAYS
 AFTER RECORDING OR THE NOTICE IS VOID.
 FS 713.13
  
 3) SUBMIT A SIGNED AND SEALED COPY OF
 THE SURVEY.
  
 4) THE SUBSURFACE SOIL REPORT IS FOR LOT
 9A. THE UNITY OF TITLE IS FOR LOTS 10A
 AND 12. THE ADDITION WILL BE THE LOT 10A
 PORTION OF THE UNIFIED LOTS.
  
 5) FAC 61G1 REQUIRES THE FIRM LICENSE
 NUMBER AND THE LICENSE NUMBER OF THE
 ARCHITECT SIGNING AND SEALING THE PLANS.
  
 6) PLEASE CORRECT THE CONSTRUCTION TYPE
 LISTED ON A1. IT IS TYPE VI CONSTRUCTION
 SEE FBC 608.
  
 7) ON SHEET A1 UNDER MASONRY REVISE #8
 (D) TO REFERENCE FBC SEC 2112, NOT SBCCI
 AND UPDATE THE SPECIFIED MASONRY
 STANDARDS TO COMPLY WITH THE 2001 FBC
 REFERENCED STANDARDS.
  
 8) SPECIFY ON THE PLANS THAT THE WWF IN
 THE SLAB IS TO BE SUPPORTED AS REQUIRED
 BY FBC 1909.3.
  
 9) SPECIFY IF THE STRUCTURE IS DESIGNED
 AS OPEN OR ENCLOSED AS REQUIRED BY FBC
 1606.1.7. IF DESIGNED USING ASCE 7-98,
 SPECIFY INTERNAL PRESSURE COEIFFICENT.
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT STATE OR LOCAL PRODUCT APPROVALS
 FOR THE FOLLOWING ITEMS:
 - SKYLIGHTS
 - CASEMENT WINDOWS
 - OVERHEAD GARAGE DOORS
  
 11) NOAS WERE SUBMITTED FOR A PROJECTED
 WINDOW, SINGLE HUNG WINDOW AND FRENCH
 DOOR WITH SIDELITES WHICH ARE NOT SHOWN
 ON THE PLANS. PLEASE SUBMIT ONLY THE
 PRODUCT APPROVALS FOR ITEMS SHOWN ON THE
 PLANS.
  
 12) A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE ROOFING.
  
 13) REVISE THE ROOF SHEATHING NAILING
 INFO ON A8. FOR A MEAN ROOF HEIGHT OF
 MORE THAN 25 FEET 8D RING SHANK NAILS
 ARE REQUIRED IN ZONE 3 AND NAIL SPACING
 IS 4"OC AT EDGES AND 6"OC INTERMEDIATE.
 SEE CITY AMENDMENTS TO FBC TABLE 2306.1.
  
 14) IN THE CONNECTOR SCHEDULE ON A8
 THERE IS NO CONNECTOR LISTED FOR MARK(K)
 AND NO FL PRODUCT APPROVAL NUMBER IS
 LISTED FOR MARK(M). PLEASE CORRECT.
  
 15) THE UPLIFT FOR MARK (I) HETA 16 IS
 1810#. PLEASE CORRECT.
  
 16) TWO CONFLICTING BUCK DETAILS ARE
 LISTED ON A8. PLEASE REMOVE ONE OF THEM.
  
 17) ON SHEET A7 A MARK FOR DETAIL E ON
 A8 IS SPECIFIED. THERE IS NO DETAIL E ON
 A8. PLEASE CORRECT.
  
 18) SPECIFY THE CONNECTION OF THE 2X6
 WALLS TO THE 72" DEEP GIRDERS AT THE
 ENTRY TOWER.
  
 19) MARK (M) AN H10 CONNECTOR IS
 SPECIFIED FOR A PORTION OF THE HALL
 CONNECTING THE ADDITION TO EXISTING THAT
 IS MASONRY AND CONCRETE. A HM9 OR EMBED
 STRAP CONNECTOR SHOULD BE USED IN THIS
 LOCATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714