| Plan Review Notes For Permit 04040670 |
| Permit Number |
04040670 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-06-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) FROM PREVIOUS REVIEW: SHOW LOCATION | | | OF WATER COOLER. WATER COOLER SHALL CON- | | | FORM TO ARI-1010. SUBMIT MANUF. SPECIFI- | | | CATION SHEETS INDICATING ARI-1010 COM- | | | PLIANCE. SECTION 410.1. | | | 2) FROM PREVIOUS REVIEW: KITCHENETTE | | | SINK. SHOW COMPLIANCE WITH SECTION | | | 11-4.24.3 KNEE CLEARANCE. AT LEAST 27" | | | AND 19" DEEP REQUIRED. - 11-4.24 DEPTH | | | OF SINK SHALL BE 6-1/2" DEEP MAX. - AND | | | 11-4.24.6 EXPOSED PIPES AND SURFACES NOT | | | SHOWN. | | | 3) A TURNING AREA COMPLYING WITH 11-4.2. | | | 3 IS REQUIRED FOR KITCHENETTE SINK. SEE | | | FIGURES 3A OR 3B. | | | 4) SEE COMMENTS FROM ELECTRICAL PLAN | | | REVIEW CONCERNING SIGNATURE REQUIREMENTS | | | FOR ENGINEER. FAC 61G15-23.002(1)(2) & | | | FS 471.025. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|