| Plan Review Notes For Permit 04040670 |
| Permit Number |
04040670 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-17 00:00:00 | *********** UNSAT ***************** | | | | | | 1)NOTE: PLEASE HAVE ENGINEER SIGN PLANS. | | | SIGNATURE DOES NOT SEEM TO BE THE SAME | | | AS PREVIOUS PLANS WE HAVE REVIEWED AND | | | PLUMB PLANS ALSO. FS 471.025 | | | PLEASE PROVIDE A COPY OF LEGAL LICENSE/ | | | AND/OR DRIVERS LICENSE TO VERIFY SIGNAT- | | | -URE. ANY PERSONNEL INFORMATION ON DL | | | MAY BE CROSSED OUT. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | SHOWN FOR NEW PANEL(S), BUT NOT FOR | | | MAINS. | | | | | | 3)NOTE: PLEASE SEE 250.66 FOR SIZING | | | OF GROUNDING ELECTRODE. | | | | | | 4)NOTE: PLEASE CORRELATE PLANS WITH | | | RISER DIAGRAM. PLANS ONLY SHOW A METER | | | ON BLDG. IS THE SERVICE IN ANOTHER | | | LOCATION? | | | | | | 5)NOTE: PLEASE LABEL CLEAR FLOOR SPACE | | | FOR PANELS IN STORAGE AREA.110.26 | | | | | | 6) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD | | | -S AT 125%(LIGHTING ETC)(LARGEST MOTORS) | | | 215.2,215.3,230.42 ETC | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|