| Plan Review Notes For Permit 04040641 |
| Permit Number |
04040641 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-19 00:00:00 | ********** PROVISO/'REVISION ********* | | | | | | 1)NOTE: PLEASE SEE METER/MAIN COMBO | | | IS BEING SHOWN AS 300A. PLEASE VERIFY | | | OCP TO FEED 200A SUB PANEL. | | | | | | 2)NOTE: IF SERVICE IS INDEED 300A'S, | | | PLEASE SEE 310.15B6 FOR MIN SEC'S TO | | | SIZE GEC PER 250.66 | | | | | | 3)NOTE; EQUIPMENT GROUNDING CONDUCTOR | | | MISSING FROM PANEL TO SUB-PANEL. 250.122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGHELECTRICAL INSPEC- | | | -TION IS CALLED IN. | | | THIS WILL BE A REVISION. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|