2004-04-19 00:00:00********** PROVISO/'REVISION *********
  
 1)NOTE: PLEASE SEE METER/MAIN COMBO
 IS BEING SHOWN AS 300A. PLEASE VERIFY
 OCP TO FEED 200A SUB PANEL.
  
 2)NOTE: IF SERVICE IS INDEED 300A'S,
 PLEASE SEE 310.15B6 FOR MIN SEC'S TO
 SIZE GEC PER 250.66
  
 3)NOTE; EQUIPMENT GROUNDING CONDUCTOR
 MISSING FROM PANEL TO SUB-PANEL. 250.122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGHELECTRICAL INSPEC-
 -TION IS CALLED IN.
 THIS WILL BE A REVISION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  