2004-04-23 00:00:00DENIED:
 1.RETURN AIR FROM BEDROOM #1 SHALL BE
 A MINIMUM OF 10".ALL AIR INTO THE
 MASTER SUITE IS TO BE INCLUDED FOR A
 TOTAL OF SUPPLY AIR INTO THAT AREA.
 REVISED 2001 FBC(M) 601.4 EXCEPTION #3.
  
 2.10" RETURN REQUIRED FROM THE NEW
 FAMILY ROOM PER 2001 FBC(M) 601.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE