| 2004-04-17 00:00:00 | ************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE CORRELATE NOTES AND |
| | DETAILS FOR SERVICE. ONE LINE MENTIONS |
| | 150A PANEL. NEW /EXISTING?RISER SHOWS |
| | EXISTING 200A SERVICE? |
| | PLEASE ALSO SEE SEC'S ARE ONLY RATED |
| | FOR 150A'S? 310.15B6 |
| | |
| | 2)NOTE: PLEASE CLARIFY LOCATION OF PANEL |
| | EXISTING OR NEW. IF MORE THAN 8' OF |
| | UNPROTECTED CONDUCTORS ARE INSIDE BLDG, |
| | A MAIN IS REQ'D OUTSIDE PROVIDING OCP. |
| | 230.70 NEC/ LOCAL AMENDMENTS. |
| | |
| | 3)NOTE: PLEASE REVISE LOAD CALCULATIONS |
| | TO NEC 220. THERE ARE MANY ITEMS SHOWN |
| | ON PANEL SCHEDULE WHICH SHOWS AN "NA" |
| | NEXT TO LOAD? IF THESE ITEMS ARE NOT |
| | GOING TO BE INSTALLED, PLEASE REMOVE |
| | FROM PANEL SCHEDULE. IF THEY ARE, PLEASE |
| | SEE NEC 220 FOR ALL MIN LOADS REQD'. |
| | PLEASE ALSO SEE NO LOAD SHOWN FOR 2ND |
| | A/C AHU HEAT?? THIS IS REQ'D. |
| | PLEASE CORRELATE W/ MECH PLANS.MECH PLAN |
| | -S SHOW TWO UNITS. |
| | |
| | 4)NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2, |
| | FOR REQ'D SD'S THROUGH-OUT RESIDENCE, |
| | INCLUDING EXISTING BEDRMS AND OUTSIDE |
| | THE EXSITNG TWO BEDROOMS.IF THESE ARE |
| | EXISTING, THEN THEY ARE REQ'D TO BE |
| | WIRED INLINE WITH ALL NEW SD'S. |
| | PLEASE SEE NFPA-72 8-1.4.2, REQ'D SD'S |
| | TO BE A MIN OF 3' FROM BATH DRS. ETC |
| | |
| | 5)NOTE: PLEASE SEE PLANS SHOULD REFER- |
| | -ENCE THE 2002 NEC. |
| | |
| | 6)NOTE: PLEASE LIST THE REQ'D ARC FAULT |
| | PROTECTED CIRCUITS PER 2002 NEC 210.12 |
| | |
| | 7)NOTE: PLEASE CLARIFY IF NEW OR EXIST- |
| | -ING REAR RECEPT PER 210.52E |
| | |
| | 8)NOTE: PLEASE VERIFY KW AND OCP SHOWN |
| | FOR WATER HEATER. MIN OCP IS 125% OF |
| | LOAD, HOWEVER, MAX OCP FOR LOAD IS 150% |
| | 422.13/ 422.11E3 |
| | |
| | 9)NOTE: PLEASE PLACE AN "E" NEXT TO |
| | PANEL SCHEDULE FOR EXISTING CIRCUITS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |