Plan Review Notes
Plan Review Notes For Permit 04040611
Permit Number 04040611
Review Stop P
Sequence Number 4
Notes
Date Text
2004-08-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED IN EACH TENNANT SPACE. ALSO
 SEE SECTION 410.1 - THIS HAS BEEN DELET-
 ED IN THIS REVISION.
 2) SHT P1.1 NEW JANITOR SINK REQUIRES A
 VENT. SECTION 901.2.1
 3) SHT P1.2 WATER HAMMER ARRESTOR IS RE-
 QUIRED FOR ICE MAKER LINE TO REFRIDG.
 SECTION 604.9
 4) SHT P1.2 FULL-OPEN VALVES SHALL BE
 INSTALLED ON THE TOP OF EVERY WATER
 DOWN-FEED PIPE. SECTION 606.1(4)
  