| Plan Review Notes For Permit 04040611 |
| Permit Number |
04040611 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-08-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) PER TABLE 403.1 A DRINKING FOUNTAIN | | | IS REQUIRED IN EACH TENNANT SPACE. ALSO | | | SEE SECTION 410.1 - THIS HAS BEEN DELET- | | | ED IN THIS REVISION. | | | 2) SHT P1.1 NEW JANITOR SINK REQUIRES A | | | VENT. SECTION 901.2.1 | | | 3) SHT P1.2 WATER HAMMER ARRESTOR IS RE- | | | QUIRED FOR ICE MAKER LINE TO REFRIDG. | | | SECTION 604.9 | | | 4) SHT P1.2 FULL-OPEN VALVES SHALL BE | | | INSTALLED ON THE TOP OF EVERY WATER | | | DOWN-FEED PIPE. SECTION 606.1(4) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|