| Plan Review Notes For Permit 04040611 |
| Permit Number |
04040611 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-05-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) FROM FIRST REVIEW: DRINKING FOUNTAIN, | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY | | | BENDING OR STOOPING. SEC 11-4.1.3(10)(A) | | | 2) WASH MACHINE SHALL HAVE A STANDPIPE | | | SECTIONS 1002.1 & 802.4 - ALSO A TRAP IS | | | REQUIRED PER SECTION 1002.1 | | | 3) FLOOR DRAIN FOR EYEWASH NOW SHOWS A | | | HORIZONTAL DRY VENT WHICH IS NOT ALLOWED | | | PER SECTION 905.3 - RUN 3" TO WALL AND | | | CONNECT FLOOR DRAIN TO WASH BASE OF VENT | | | STACK. SEE RED LINE DRAWING FOR EXAMPLE | | | 4) SHT P2.1 SHOW WATER HAMMER ARRESTORS | | | ON WATER RISER DIAGRAM WHERE REQUIRED BY | | | SECTION 604.9 - SEE RED LINE ON DRAWING | | | FOR EXAMPLE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|