Plan Review Notes
Plan Review Notes For Permit 04040611
Permit Number 04040611
Review Stop P
Sequence Number 1
Notes
Date Text
2004-04-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED IN EACH TENANT SPACE. ALSO SEE
 SECTION 410.1. SUBMIT DETAIL PER SECTION
 11-4.15 AND SECTION 11-4.1.3(10)(A) PRO-
 VISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 2) DEMO SHEET - ALL CAPPED AND DEMO'D
 PIPING SHALL BE INSPECTED PRIOR TO COVER
 ING.
 3) SHT P1.1 WASH MACHINE SHALL NOT DIS-
 CHARGE INTO THE HORIZONTAL WET VENT FOR
 THE BATHROOM GROUPS. SECTION 909.1. WASH
 MACHINE SHALL CONNECT DOWNSTREAM OF THE
 FIXTURES FOR THE BATHROOM.
 4) SHT P1.1 WASH MACHINE SHALL HAVE A
 STANDPIPE, SECTIONS 1002.1 & 802.4.
 5) SHT P1.1 WASH MACHINE SHALL HAVE A
 CLEANOUT 4' ABOVE THE FLOOR ON THE STACK
 SECTION 708.10.
 6) SHT P1.1 FLOOR DRAIN FOR EYEWASH RE-
 QUIRES A VENT PER SECTION 901.2.1
 7) SHT P1.1 SANITARY RISER DIAGRAM AND
 THE FLOOR PLAN. IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF THE DRAINAGE SYS-
 TEM, DEAD ENDS SHALL BE PROHIBITED. ALL
 BRANCH LINES SHALL BE CAPPED AT THE BLDG
 DRAIN. SECTION 704.5
 8) SHT P2.1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS ARE REQUIRED FOR THE
 WASH MACHINE AND ICE MAKER PER SECTION
 604.9 AND SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING PER PDI-WH 201 AND MANUF. INST-
 ALLATION INSTRUCTIONS.
  