| Plan Review Notes For Permit 04040611 |
| Permit Number |
04040611 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-23 00:00:00 | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | 1.INDICATE NEW OR EXISTING DUCT SMOKE | | | DETECTORS.PLEASE NOTE, SYSTEMS THAT | | | HAVE THE DESIGN CAPACITY GREATER THAN | | | 2,000 CFM SHALL HAVE DUCT SMOKE DETECTOR | | | | | | 2.PLAN SHEET M1.1 FIRE DAMPER APPEARS | | | TO BE LOCATED OUTSIDE OF THE WALL, | | | PLEASE CLARIFY. | | | | | | 3.SEE ALSO COMMENT #9 BY ASST FIRE | | | MARSHAL, MIKE CARSILLO. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|