Plan Review Notes
Plan Review Notes For Permit 04040611
Permit Number 04040611
Review Stop M
Sequence Number 1
Notes
Date Text
2004-04-23 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.INDICATE NEW OR EXISTING DUCT SMOKE
 DETECTORS.PLEASE NOTE, SYSTEMS THAT
 HAVE THE DESIGN CAPACITY GREATER THAN
 2,000 CFM SHALL HAVE DUCT SMOKE DETECTOR
  
 2.PLAN SHEET M1.1 FIRE DAMPER APPEARS
 TO BE LOCATED OUTSIDE OF THE WALL,
 PLEASE CLARIFY.
  
 3.SEE ALSO COMMENT #9 BY ASST FIRE
 MARSHAL, MIKE CARSILLO.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.