| Plan Review Notes For Permit 04040611 |
| Permit Number |
04040611 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-08 00:00:00 | 1) ALL DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) DEMOLITION DERBIS SHALL BE REMOVED | | | FROM THE BUILDING DAILY. | | | | | | 3) ALL EXITS SHALL REMAIN CLEAR | | | DURING DEMOLITION. | | | | | | 4) PLEASE INDICATE WHAT THE PROCEDURE | | | ROOMS WILL BE USED FOR. | | | | | | 5) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 6) PLEASE PROVIDE MORE DETAILS ON | | | NEW EMERGENCY GENERATOR. | | | | | | 7) DUCT SMOKE DETECTORS ARE REQUIRED | | | IN AIR HANDLING SYSTEMS THAT EXCEED | | | 2000 CFM. | | | | | | 8) PLEASE INDICATE PORTABLE FIRE | | | EXTINGUISHERS LOCATED WITHIN THE | | | SPACE. | | | | | | 9) ANY OXYGEN SYSTEMS OR PORTABLE | | | CYLINDERS PLANNED FOR THE SITE. | | | | | | 10) PLEASE INDICATE PROPOSED OCCUPANT | | | LOADS FOR THE SPACE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|