2004-04-08 00:00:001) ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEMOLITION DERBIS SHALL BE REMOVED
 FROM THE BUILDING DAILY.
  
 3) ALL EXITS SHALL REMAIN CLEAR
 DURING DEMOLITION.
  
 4) PLEASE INDICATE WHAT THE PROCEDURE
 ROOMS WILL BE USED FOR.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 6) PLEASE PROVIDE MORE DETAILS ON
 NEW EMERGENCY GENERATOR.
  
 7) DUCT SMOKE DETECTORS ARE REQUIRED
 IN AIR HANDLING SYSTEMS THAT EXCEED
 2000 CFM.
  
 8) PLEASE INDICATE PORTABLE FIRE
 EXTINGUISHERS LOCATED WITHIN THE
 SPACE.
  
 9) ANY OXYGEN SYSTEMS OR PORTABLE
 CYLINDERS PLANNED FOR THE SITE.
  
 10) PLEASE INDICATE PROPOSED OCCUPANT
 LOADS FOR THE SPACE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910