Plan Review Notes
Plan Review Notes For Permit 04040611
Permit Number 04040611
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-18 00:00:00************* UNSAT ************
  
 PLEASE SEE FIRE REVIEW COMMENTS AS THEY
 WILL CAUSE CHANGES TO E-SHEETS.
  
 1)NOTE: PLEASE SUBMIT MORE INFORMATION
 ON GENERATOR. ALL SPECS TO BE SUBMITTED.
 PLEASE CLARIFY WHERE DISC MEANS IS FOR
 POWER COMING INTO BLDG FROM GEN.??
 225.31.
 PLEASE ALSO SEE 230.76,230.79,110.27
 FOR DISC RATING ETC.
 ATS AND E-PANEL MAY NOT BE INSTALLED IN
 A "STORAGE" ROOM. 110.26,408.7 ETC.
 ROOM MUST CHANGE TO A DEDICATED ELEC/
 MECH RM WITH SIGNAGE ETC. 230.2E
 PLEASE INDICATE GROUNDING FOR GEN.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/ EXT LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  