| Notes |
| Date |
Text |
| 2004-04-18 00:00:00 | ************* UNSAT ************ | | | | | | PLEASE SEE FIRE REVIEW COMMENTS AS THEY | | | WILL CAUSE CHANGES TO E-SHEETS. | | | | | | 1)NOTE: PLEASE SUBMIT MORE INFORMATION | | | ON GENERATOR. ALL SPECS TO BE SUBMITTED. | | | PLEASE CLARIFY WHERE DISC MEANS IS FOR | | | POWER COMING INTO BLDG FROM GEN.?? | | | 225.31. | | | PLEASE ALSO SEE 230.76,230.79,110.27 | | | FOR DISC RATING ETC. | | | ATS AND E-PANEL MAY NOT BE INSTALLED IN | | | A "STORAGE" ROOM. 110.26,408.7 ETC. | | | ROOM MUST CHANGE TO A DEDICATED ELEC/ | | | MECH RM WITH SIGNAGE ETC. 230.2E | | | PLEASE INDICATE GROUNDING FOR GEN. | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULE. | | | PLEASE SEE 700.12E FOR CIRCUITING OF | | | EM/ EXT LTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|