| 2004-04-18 00:00:00 | *********** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SUBMIT A PANEL SCHEDULE |
| | SHOWING ALL MIN CIRCUITS. |
| | |
| | 2) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 3)NOTE: PLEAS LIST ARC FAULT PER 2002 |
| | NEC. |
| | |
| | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 5 )NOTE: PLEASE SEE MISSING REQ'D EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210.70 AND LS-101 5-8 |
| | PLEASE ALSO SHOW SW TO CONTROL WHICH LTS |
| | SHOW STAIRWAY/ LTS ETC. |
| | |
| | 6) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 7) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 8 )NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | PER PER 220, 215.5 |
| | |
| | 9)NOTE:PLEASE CLARIFY IF EXIST PANEL |
| | SHOWN IS TO REMAIN? PLEASE SEE 110.26 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |