| Plan Review Notes For Permit 04040562 |
| Permit Number |
04040562 |
|
| Review Stop |
E |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2006-05-14 00:00:00 | *** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE MAX OCP DOES NOT | | | CORRELATE WITH MECH PLANS. PLEASE SEE | | | 424.3B FOR MIN OCP TO BE 125%, HOWEVER | | | PLEASE KNOW, TYOICALLY THE MAX OCP IS | | | 150% OR NAMEPLATE. | | | PLEASE ADJUST AND CORRLEATE. | | | PLEASE ALSO ADJUST MAIN LOAD CALCS. | | | | | | | | | ** PLEASE SEE ANY MECHANICAL REVIEW | | | NOTES AS THESE MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|