| Plan Review Notes For Permit 04040562 |
| Permit Number |
04040562 |
|
| Review Stop |
M |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2006-05-15 00:00:00 | DENIED: | | | 1.PLAN SHEET M-2.1, EF-1 IS NOW | | | TERMINATING AT THE FIRST FLOOR WALL. | | | PLAN SHEET M-2.2 AND M-2.3 INDICATE EF-1 | | | STILL TERMIATING AT THE ROOF.PLEASE | | | REVISE PLANS TO REFLECT THE PROPER | | | TERMINATION. | | | | | | 2.PLAN SHEET M-2.1, SUPPLY & RETURN | | | DUCTS TO RTU-1 ARE REQUIRED TO HAVE FIRE | | | DAMPERS AT THE FLOOR WHERE THEY LEAVE | | | THE RATED SHAFT IN ACCORDANCE WITH 1999 | | | NFPA 90A 3-3.4.4 & 2001 FBC 705.6.4. | | | | | | 3.COMMENT #2 ALSO APPLIES TO PLAN | | | SHEET M-2.2 2ND FLOOR WHERE THE DUCT | | | PASSES THROUGH THE RATED FLOOR FROM | | | RTU-2.PLEASE REVISE PLANS TO INDICATE | | | ALL FIRE DAMPER/ACCESS DOORS FOR ALL | | | RTU'S. | | | | | | 4.PLEASE NOTE, SHOULD THE EXHAUST | | | SHAFTS FOR EF-3 & EF-2 BE A SUB-DUCT | | | METHOD, FIRE DAMPERS WILL NOT BE | | | REQUIRED.PLEASE CLARIFY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|