| Plan Review Notes For Permit 04040562 |
| Permit Number |
04040562 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-07-07 00:00:00 | PROVISO: | | | RESPONSE TO PROVISO DATED JUNE 24,2004; | | | SHAFT INDICATED ON THE ARCHITECTURAL | | | DRAWINGS.PLAN DOES NOT INDICATE FIRE | | | DAMPERS ON THE DUCT PENTRATING THE SHAFT | | | WALLS ON FLOORS 1 THROUGH 3. | | | | | | FAN SHUT DOWN BY DUCT SMOKE DETECTORS | | | REQUIRED PER 2001 FBC(M) 606.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|