| 2004-07-16 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 6/18/04: |
| | |
| | 1) NOTICE OF COMMENCEMENT. |
| | COMMENT RESPONSE OF 6/24/04 IS NOTED. |
| | THE SUBMITTED NOTICE OF COMMENCEMENT IS |
| | FOR "REPLACEMENT OF FIRE STAIRS" UNDER |
| | PERMIT# 04020595.THAT SCOPE OF WORK |
| | AND PERMIT NUMBER ARE NOT RELEVANT. |
| | THE NOTICE OF COMMENCEMENT SHALL BE |
| | RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| | AND A COPY SUBMITTED TO THIS OFFICE |
| | BEFORE A PERMIT CAN BE ISSUED.BLANK |
| | FORMS ARE AVAILABLE FROM THIS OFFICE. |
| | |
| | 2) IMPACT FEES. |
| | CONTRARY TO THE COMMENT RESPONSE OF |
| | 6/24/04, NO RECEIPT FOR IMPACT FEES WAS |
| | SUBMITTED AND THE PLANS WERE NOT STAMPED |
| | AS 'ASSESSED'. THE PLANS SHALL BE TAKEN |
| | TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| | STAMPED AT THAT OFFICE AND A COPY OF THE |
| | PAID RECEIPT SUBMITTED TO THE CITY OF |
| | WEST PALM BEACH DEPT OF CONSTRUCTION |
| | SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 5) SITE SURVEY. |
| | COMMENT RESPONSE OF 6/24/04 IS NOTED. |
| | ONLY TWO COPIES OF THE SITE SURVEY |
| | DRAWING WERE SUBMITTED.SUBMIT A THIRD |
| | COPY FOR THE THRESHOLD INSPECTOR AS |
| | REQUIRED BY COMMENT 34. |
| | |
| | 7) FBC 13-103.1.2 ENERGY CODE COMPLIANCE |
| | FORM.COMMENT RESPONSE OF 6/24/04 IS |
| | NOTED. THE COMMENT HAS NOT BEEN PROPERLY |
| | ADDRESSED.THE FOLLOWING ARE REPEATED: |
| | (B) THE PROJECT INFORMATION ON EACH COPY |
| | OF SHEET 1 SHALL INCLUDE THE CORRECT |
| | PROJECT ADDRESS (307 EVERNIA ST) AND ZIP |
| | CODE (33401), THE PERMIT NUMBER |
| | (04040562) AND THE OWNER'S NAME. |
| | (C) FBC 13-103.1.1.1THE ARCHITECT'S |
| | LICENSE NUMBER HAS NOT BEEN ADDED TO |
| | SHEET 2 OF EACH COPY OF THE ENERGY CODE |
| | COMPLIANCE FORM |
| | (D) SUBMIT A THIRD COPY OF THE ENERGY |
| | CODE COMPLIANCE FORM AS REQUIRED BY |
| | COMMENT 34. |
| | |
| | 29) PRODUCT APPROVALS |
| | THE SUBMITTED PRODUCT APPROVALS HAVE |
| | BEEN REVIEWED AND FOUND TO INCLUDE |
| | PRODUCTS WITH ADEQUATE DESIGN PRESSURES |
| | TOGETHER WITH PRODUCTS NOT APPROPRIATE |
| | FOR USE ON THIS PROJECT.REVIEW THE |
| | PRODUCT APPROVAL NOA SHEETS AND MARK/ |
| | HIGHLIGHT, AS APPROPRIATE, TO IDENTIFY |
| | WHICH PRODUCT OPTIONS/MATERIALS/SIZES |
| | ARE TO BE USED.THIS APPLIES TO ALL |
| | THREE COPIES OF EACH PRODUCT APPROVAL. |
| | |
| | 34) FBC* 105.13.1SPECIAL INSPECTOR. |
| | ONE COPY THE SUBMITTED STRUCTURAL |
| | INSPECTION PLAN HAS BEEN FORWARDED TO |
| | HAROLD) ACTING INSPECTION SEVICES |
| | MANAGER FOR REVIEW/RECORDS. A SIGNED AND |
| | SEALED COPY OF THE SPECIAL INSPECTOR |
| | AGREEMENT AND AFFADAVIT (GUIDELINES AND |
| | BLANK FORMS ATTACHED) SHALL BE SUBMITTED |
| | BEFORE THE PERMIT CAN BE ISSUED.CALL |
| | HAROLD PISKURA (TEL: 561 805 6711) AS HE |
| | REQUIRES A PRE-CONSTRUCTION MEETING WITH |
| | THE OWNER, CONTRACTOR, INSPECTION |
| | COMPANY AND ON-SITE INSPECTOR. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |