| 2006-05-12 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | REVISION SUBMITTED ON 4/14/06 FOR |
| | SKYLIGHT PRODUCT APPROVAL AND |
| | PLANS/PRODUCT APPROVAL FORAPPLICATION |
| | OFROOFING SYSTEM TO THE METAL DECK |
| | OMITTING THE CONCRETE SLAB. |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | |
| | 1) SHEETS A3.1 AND A3.2 WERE REVISED BUT |
| | SHEET A1.1.4.1, DETAILS 05 AND 08, AND |
| | SHEET A3.2.1, DETAILS 01, 02 1ND 06 ALSO |
| | MAKE SPECIFIC REFERENCE TO 'CONCRETE |
| | SLAB ON METAL DECK'.THESE SHEETS MUST |
| | ALSO BE AMENDED FOR CONSISTENCY. |
| | |
| | 2) THE REVISED SHEETS REFER TO 'BUILT UP |
| | ROOF' WHILE THE SUBMITTED PRODUCT |
| | APPROVAL IS FOR 'MODIFIED BITUMEN ROOF |
| | SYSTEM'.AMEND THE PLANS TO CORRECTLY |
| | STATE THE TYPE OF ROOF SYSTEM TO BE USED |
| | (I.E. MODIFIED BITUMEN ROOF). |
| | |
| | 3) RATIONAL ANALYSIS REQUIRED PER |
| | MODIFIED BITUMEN ROOF PRODUCT APPROVAL. |
| | THE SUBMITTED GAF MODIFIED BITUMEN |
| | ROOFING PRODUCT APPROVAL NOA# 03-0430.12 |
| | WAS MISSING SHEETS 1 TO 3 AND THE STATE |
| | PRODUCT APPROVAL COVER SHEET FL# 617-R1. |
| | THESE HAVE BEEN PRINTED FOR YOU TO |
| | EXPEDITE THE PROCESS.ON SHEET 13 OF |
| | THE NOA, THE STATED MAXIMUM DESIGN |
| | PRESSURE IS -60 PSF, WHICH IS ADEQUATE |
| | TO RESIST THE -43 PSF CALCULATED |
| | PRESSURE, STATED ON STRUCTURAL PLAN |
| | SHEET S1.0, FOR ZONE 1 (FIELD) OF THE |
| | ROOF.AS STATED ON SHEET 13 OF THE NOA, |
| | THAT IS ACHIEVED USING A FASTENER |
| | DENSITY OF 1 FASTENER PER 1.5 SQUARE |
| | FEET FOR ATTACHMENT OF THE INSULATION TO |
| | THE METAL DECK.HOWEVER, FOR ZONES 2 |
| | AND 3, STRUCTURAL PLAN SHEET S1.0 STATES |
| | THAT THE CALCULATED PRESSURES ON THE |
| | BUILDING ARE -73 PSF AND -107 PSF |
| | RESPECTIVELY.ALTHOUGH THESE PRESSURES |
| | EXCEED THE ALLOWABLE -60 PSF MAXIMUM |
| | DESIGN PRESSURE STATED ON SHEET 13 OF |
| | THE NOA, THAT SHEET REFERS TO GENERAL |
| | LIMITATION #7.ON SHEET 31 OF THE NOA, |
| | GENERAL LIMITATION #7 ALLOWS RATIONAL |
| | ANALYSIS TO DETERMINE THE INCREASED |
| | FASTENER DENSITY REQUIRED TO RESIST THE |
| | -73 PSF AND -107 PSF WIND PRESSURES IN |
| | ZONES 2 AND 3.NO RATIONAL ANALYSIS WAS |
| | SUBMITTED.SUBMIT CALCULATIONS STATING |
| | THE FASTENER INSULATION LAYER FASTENER |
| | DENSITY. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6652ROBERT BROWN |