Plan Review Notes
Plan Review Notes For Permit 04040562
Permit Number 04040562
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2004-06-03 00:00:001) MORE DETAILS REQUIRED FOR ALUMINUM
 ROLLING SHUTTERS AND HOW DO THEY
 FUNCTION. WHAT ARE THERE PURPOSE.
  
 2) FIRE ALARM CIRCUITS SHALL BE CLASS
 A, STYLE D OR BE FULLY ADDRESSABLE.
 END OF LINE RESISTORS ARE SHOWN.
 PLEASE ADVISE.
  
 3) EXIT SIGN MISSING FROM REAR DOOR
 ON PAGE E-3.1.
  
 4) EXIT SIGN MISSING FROM PAGE E-2.2
 NEAR DOOR LEADING TO EXTERIOR.
  
 5) FIRE DEPARTMENT CONNECTION SHOWN
 IN TWO DIFFERENT LOCATIONS. ONE
 INDICATES IT ON THE BACKFLOW THE
 OTHER LOCATION SHOWS IT ON THE
 BUILDING. PLEASE ADVISE. ALSO
 ACCORDING TO DEAN LAUDERMILK OF
 UTILITIES THE BACKFLOW IS IN THE
 WRONG LOCATION. PLEASE CONSULT WITH
 HIM WITH REGARDS TO THI MATTER.
  
 6) SOME GENERATOR NOTES STILL EXIST
 ON THE ELECTRICAL PLANS. PLEASE
 REMOVE THESE FROM THE DRAWINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910