| Plan Review Notes For Permit 04040562 |
| Permit Number |
04040562 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-06-03 00:00:00 | 1) MORE DETAILS REQUIRED FOR ALUMINUM | | | ROLLING SHUTTERS AND HOW DO THEY | | | FUNCTION. WHAT ARE THERE PURPOSE. | | | | | | 2) FIRE ALARM CIRCUITS SHALL BE CLASS | | | A, STYLE D OR BE FULLY ADDRESSABLE. | | | END OF LINE RESISTORS ARE SHOWN. | | | PLEASE ADVISE. | | | | | | 3) EXIT SIGN MISSING FROM REAR DOOR | | | ON PAGE E-3.1. | | | | | | 4) EXIT SIGN MISSING FROM PAGE E-2.2 | | | NEAR DOOR LEADING TO EXTERIOR. | | | | | | 5) FIRE DEPARTMENT CONNECTION SHOWN | | | IN TWO DIFFERENT LOCATIONS. ONE | | | INDICATES IT ON THE BACKFLOW THE | | | OTHER LOCATION SHOWS IT ON THE | | | BUILDING. PLEASE ADVISE. ALSO | | | ACCORDING TO DEAN LAUDERMILK OF | | | UTILITIES THE BACKFLOW IS IN THE | | | WRONG LOCATION. PLEASE CONSULT WITH | | | HIM WITH REGARDS TO THI MATTER. | | | | | | 6) SOME GENERATOR NOTES STILL EXIST | | | ON THE ELECTRICAL PLANS. PLEASE | | | REMOVE THESE FROM THE DRAWINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|