2004-06-15 00:00:00************ UNSAT **************
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE COMMENTS BELOW.
  
 1)NOTE: PLEASE SEE RISER STILL SHOWS
 EQUIPMENT GROUNDING CONDUCTORS BEING
 INSTALLED FROM METER TO FIRST MEANS OF
 DISCONNECT.PREVIOUS COMMENT MENTIONS
 "NO, EQUIPMENT GRNDS" 250.24 /250.6
 RESPONSE MENTIONS SEE NOTES, 17/19.
 THE EQUIPMENT GRNDS SHOWN MUST BE
 REMOVED.
  
 2)NOTE: PLEASE SEE SEC'S FEEDING 150A
 HOUSE PANEL ARE SHOWN AS 1/0'S. THIS IS
 OK, PLEASE SEE CONDUCTOR SIZE FROM
 METER TO PANEL ARE SHOWN AS 4/0'S. THIS
 IS PERMITTED HOWEVER OVERSIZED. THIS IS
 ONLY A NOTE AND MAY BE DONE. HOWEVER, IF
 SHOWN ON RISER THEN THEY MUST BEINSTALL-
 -ED OR PLANS WILL NEED TO BE REVISED.
 PANEL SCHEDULE SHOWS 1/0'S ALSO.
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS,
 PERTAINING TO MISSING EM/EXT LTS AT
 DIFFERENT LOCATIONS. THIS WILL HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 4)NOTE: PLEASE SEE THERE ARE STILL MANY
 SHEETS CONTAINING NOTES ABOUT GENERATOR.
 REPLY LETTER MENTIONS ALL GEN/ATS ETC TO
 BE ELIMINATED. PLEASE REMOVE NOTES.
  
 5)NOTE: PLEASE ADJUST NOTE FOR GROUNDING
 ELECTRODE TO "FOOTER STEEL". RISER SHOWS
 STRUCT STEEL, WHICH IS REQUIRED IF IN
 CONSTRUCTION. PLEASE SEE 250.50
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS OUT
 OF SETS. ONLY INSERT NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 THIS WILL HELP WITH THE REVIEW PROCESS.
 THIS WAS REQUESTED ON PREVIOUS REVIEW.
  
 PLEASE SEE BLDG REVIEW COMMENTS FOR
 POSSIBLE "THRESHOLD" BLDG. THREE SETS
 OF PLANS WOULD BE NEEDED FOR STAMPING.
  
 PLEASE SEE ATTACHED COPY OF FS 553-80(2)
 (B). THIS IS A NOTICE GIVEN WITH RESPECT
 TO DESIGN PROFESSIONAL. THIS IS ONLY
 GIVEN AS A NOTICE AND DOES NOT AFFECT
 THIS REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]