| 2006-12-09 15:20:37 | **** UNSAT ***** |
| | |
| | 1) NOTE: PLEASE SEE 250.66 FOR GROUNDING ELECTRODE |
| | CONDUCTOR. PLEASE SEE THIS WAS REDLINED ON PREVIOUS |
| | REVISIONS WHICH WERE SUBMITTED HOWEVER THIS HAS NOT |
| | BEEN CORRECTED. PLEASE SEE AS THE SEC'S HAVE INCREASED, |
| | SO SHALL THE GEC. |
| | |
| | 2) NOTE: PLEASE SEE A PANEL BEING SHOWN AT THE DRIVE |
| | THROUGH WILL BE REQUIRED TO MEET 225.31-225.39. PLEASE |
| | SEE 225.32 AND HOW THIS EQUIPMENT IS READILY |
| | ACCESSIBLE. |
| | ** PLEASE SEE THAT THE ORIGINAL PLANS ISSUED FOR PERMIT |
| | WERE REDLINED FOR THIS, HOWEVER THE INSTALLATION WAS |
| | DONE PER REDLINED CODES ON PLANS. PLEASE SEE THIS SHALL |
| | BE REVISED ON THE PERMITTED PLANS FOR THE DETACHED BLDG |
| | ALSO. |
| | PLEASE SUPPLY DETAIL FROM MANUFACTURE, SPECS/CUT |
| | SHEETS. 110.3, 90.7 |
| | |
| | 3) NOTE: PLEASE SEE 250.32 FOR GROUNDING AT THE |
| | DETACHED BUILDING. |
| | PLEASE SHOW IN DETAIL THE SYSTEM. |
| | **PLEASE KNOW THE PLANS FOR THE DETACHED BUILDING WILL |
| | ALSO BE REQUIRED TO BE UPDATED TO THESE COMMENT AND |
| | CHANGES MADE. |
| | |
| | 4) NOTE: PLEASE CORRELATE RISER AND PANEL SCHEDULE FOR |
| | NEW PANEL FEEDERS. PLEASE SEE PANEL "A" WHICH SHOWS |
| | 1/0'S AND RISER SHOWS 4/0'S. PLEASE ALSO INDICATE HOW |
| | THESE SIZE CONDUCTORS WILL BE TERMINATED INTO THE PANEL |
| | AND BREAKERS AS SHOWN. |
| | (ADAPTERS OF SOME SORT)? |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |