Plan Review Notes
Plan Review Notes For Permit 04040562
Permit Number 04040562
Review Stop B
Sequence Number 12
Notes
Date Text
2005-02-22 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL ON 2/22/05 FOR
 GRADE BEAM CALCULATION
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 104.2.1.2THE CALCULATIONS DO
 NOT INCLUDE A TUNNEL LOCATION PLAN.
 SUBMIT A PLAN SHOWING THE SIZE, LOCATION
 AND ORIENTATION OF THE TUNNEL AND ITS
 POSITION RELATIVE TO PILE CAPS P8, P6A
 AND P6 (AT GRID C1).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]