Plan Review Notes
Plan Review Notes For Permit 04040562
Permit Number 04040562
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-04-09 00:00:001) ELECTRONIC SWITCHES, CHAIN AND
 LOCK WILL BE REQUIRED ON THE FIRE
 LINE BACKFLOW DEVICE.
  
 2) THE FIRE DEPARTMENT CONNECTION
 SHALL HAVE KNOX-BOX LOCKING CAPS
 INSTALLED.
  
 3) A KNOX-BOX WILL BE REQUIRED.
  
 4) THE NEW FIRE ALARM SYSTEM SHALL BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 5) ALL SHAFTS THAT ARE LARGE ENOUGH FOR
 PERSONS TO FALL INTO MUST BE MARKED
 SHAFTWAY WITH SIX HIGH LETTERS.
  
 6) EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 7) TEMPORARY STANDPIPE SYSTEMS ARE
 REQUIRED WHEN THE BUILDING REACHES
 THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 8) PLEASE PROVIDE MORE DETAILS FOR THE
 PROPOSED GENERATOR LOCATED ON THE
 ROOF.
  
 9) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 10) ELEVATOR WARNING SIGNS ARE REQUIRED
 ON EVERY FLOOR NEAR THE ELEVATOR
 OPENING.
  
 11) BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS. CERTAIN RESTRICTIONS WILL
 APPLY. PLEASE SEE APPENDIX F, LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING CODE.
  
 12) ARCHITECTURAL TRIM LOCATED IN THE
 CITY FIRE LIMTS SHALL BE
 NONCOMBUSTIBLE. FOAM TRIM NOTED ON ROOF
 DETAILS PAGE.
  
 13) BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION. A MINIMUM OF 6"
 NUMBERS REQUIRED.
  
 14) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL HANDRAILS
 AND GUARDRAILS.
  
 15) IS THE BUILDING A SINGLE OR
 MULTIPLE TENANT ARRANGEMENT. PLEASE
 ADVISE.
  
 16) PLEASE INDICATE RISER SIZES FOR
 STAIR # 2.
  
 17) PLEASE DISPLAY SPHERE RESISTANCE
 ON HANDRAIL/GUARDRAIL @ STAIR DETAIL.
  
 18) DUCT SMOKE DETECTORS ARE REQUIRED
 IN ALL AIR HANDLING SYSTEMS OVER 2000
 CFM. WHEN ACTIVATED, THESE SYSTEMS SHALL
 CAUSE THESE SYSTEMS TO STOP AND
 ACTIVATE THE FIRE ALARM SYSTEM.
  
 19) EMERGENCY LIGHTING REQUIRED IN FIRE
 PUMP ROOM.
  
 20) 2 1/2 TO 1 1/2 REDUCERS REQUIRED
 ON STANDPIPE SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910