| Date |
Text |
| 2004-04-09 00:00:00 | 1) ELECTRONIC SWITCHES, CHAIN AND |
| | LOCK WILL BE REQUIRED ON THE FIRE |
| | LINE BACKFLOW DEVICE. |
| | |
| | 2) THE FIRE DEPARTMENT CONNECTION |
| | SHALL HAVE KNOX-BOX LOCKING CAPS |
| | INSTALLED. |
| | |
| | 3) A KNOX-BOX WILL BE REQUIRED. |
| | |
| | 4) THE NEW FIRE ALARM SYSTEM SHALL BE |
| | UL LISTED FOR CENTRAL STATION SERVICE. |
| | |
| | 5) ALL SHAFTS THAT ARE LARGE ENOUGH FOR |
| | PERSONS TO FALL INTO MUST BE MARKED |
| | SHAFTWAY WITH SIX HIGH LETTERS. |
| | |
| | 6) EXIT STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 7) TEMPORARY STANDPIPE SYSTEMS ARE |
| | REQUIRED WHEN THE BUILDING REACHES |
| | THREE STORIES OR THIRTY FEET IN |
| | HEIGHT. |
| | |
| | 8) PLEASE PROVIDE MORE DETAILS FOR THE |
| | PROPOSED GENERATOR LOCATED ON THE |
| | ROOF. |
| | |
| | 9) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS. |
| | |
| | 10) ELEVATOR WARNING SIGNS ARE REQUIRED |
| | ON EVERY FLOOR NEAR THE ELEVATOR |
| | OPENING. |
| | |
| | 11) BUILDING IS LOCATED IN THE CITY |
| | FIRE LIMITS. CERTAIN RESTRICTIONS WILL |
| | APPLY. PLEASE SEE APPENDIX F, LOCAL |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE. |
| | |
| | 12) ARCHITECTURAL TRIM LOCATED IN THE |
| | CITY FIRE LIMTS SHALL BE |
| | NONCOMBUSTIBLE. FOAM TRIM NOTED ON ROOF |
| | DETAILS PAGE. |
| | |
| | 13) BUILDING ADDRESS REQUIRED ON |
| | PROPER ELEVATION. A MINIMUM OF 6" |
| | NUMBERS REQUIRED. |
| | |
| | 14) PLEASE PROVIDE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR ALL HANDRAILS |
| | AND GUARDRAILS. |
| | |
| | 15) IS THE BUILDING A SINGLE OR |
| | MULTIPLE TENANT ARRANGEMENT. PLEASE |
| | ADVISE. |
| | |
| | 16) PLEASE INDICATE RISER SIZES FOR |
| | STAIR # 2. |
| | |
| | 17) PLEASE DISPLAY SPHERE RESISTANCE |
| | ON HANDRAIL/GUARDRAIL @ STAIR DETAIL. |
| | |
| | 18) DUCT SMOKE DETECTORS ARE REQUIRED |
| | IN ALL AIR HANDLING SYSTEMS OVER 2000 |
| | CFM. WHEN ACTIVATED, THESE SYSTEMS SHALL |
| | CAUSE THESE SYSTEMS TO STOP AND |
| | ACTIVATE THE FIRE ALARM SYSTEM. |
| | |
| | 19) EMERGENCY LIGHTING REQUIRED IN FIRE |
| | PUMP ROOM. |
| | |
| | 20) 2 1/2 TO 1 1/2 REDUCERS REQUIRED |
| | ON STANDPIPE SYSTEM. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |