Plan Review Notes
Plan Review Notes For Permit 04040475
Permit Number 04040475
Review Stop M
Sequence Number 1
Notes
Date Text
2004-04-15 00:00:00DENIED:
 PLAN SHEET 3 OF 6 INDICATES 36" H.
 PLATFORM.PLEASE SUBMIT MOUNTING
 DETAIL FOR THE AHU.PLAN ALSO
 INDICATES A 25 1/2" X 19 1/2" R/A
 GRILLE, RETURN AIR MUST BE DUCTED INTO
 THE AHU OR PLENUM.BEDROOM #5/STUDY
 DOES NOT INDICATE A RETURN AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.