2004-04-13 00:00:00***** UNSAT ***
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MAIN/ SERVICE PER 110.9.
 MAINS/BRKRS AND PANEL ARE REQ'D TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
  
 2)NOTE: PLEASE PROVIDE MORE INFORMATION
 FOR FEED TO HOUSE PANEL AS NOTED ON
 RISER. DETACHED? GROUNDING? MEANS OF
 DISC? 225.31,250.32 ETC. 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  