| Plan Review Notes For Permit 04031743 |
| Permit Number |
04031743 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-02-23 00:00:00 | MECH. NOTES 1.AND 2.WERE ANSEWERED, | | | A/C OK. | | | PAT RAFTER 561/805/6728 | | | PLEASE CALL IF ENY QUESTIONS. | | 2005-02-14 00:00:00 | 1. A.H.U. #3R/A FROM LIBRARY NOT | | | REFLECTED ON PLAN .2001 FBC/M 601.4 | | | BALANCED RETURN AIR. | | | | | | 2. A.H.U. #1 AND #2 REQUIRE DUCTED R/A | | | THROUGH NON LIVING AREA TO A.H.U. AND | | | SECONT FLOOR PLAN REFLECTS DOORS | | | SEPERATING LIVING ROOM/LOGGIA ROOM FROM | | | HALL WAY. | | | PLEASE CLEARFIE R/A ROUTING. | | | PAT RAFTER 561/805/6728. | | | IF THEAR ENY QUISTION PLEASE CALL. |
|