| Date |
Text |
| 2004-11-24 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1) SANITARY RISER DIAGRAM DOES NOT MEET |
| | CODE REQUIREMENTS, NOR DOES IT REFLECT |
| | THE FLOOR PLAN. |
| | A) THE WASH MACHINE REQUIRES A CLEANOUT |
| | 4 FEET ABOVE THE FLOOR FOR ACCESS, AND A |
| | STANDPIPE. SECTIONS 708.10, & 1002.1 |
| | B) THE FIRST FLOOR BATHROOM SHOWS THE |
| | TUB AND LAV ON THE SAME WALL AND THE LAV |
| | ON THE LEFT OF THE W/C ON THE RISER |
| | DIAGRAM, BUT ON THE FLOOR PLAN THE TUB |
| | AND LAV ARE ON DIFFERENT WALLS. SECTION |
| | 104.2.1. |
| | C) THE FIRST FLOOR W/C SHALL NOT BE |
| | DOUBLE TRAPPED. SECTION 1002.1. THE W/C |
| | HAS AN INTEGRAL TRAP. |
| | D) TWO BIDETS SHOWN ON THE FLOOR PLAN |
| | ARE NOT SHOWN ON THE RISER DIAGRAM. |
| | SECTION 104.2.1 |
| | E) ALL W/C'S SHALL NOT BE DOUBLE |
| | TRAPPED. SECTION 1002.1 |
| | F) THE BATHROOM LAYOUTS ON THE RISER |
| | DIAGRAM DO NOT REFLECT THE FLOOR PLAN. |
| | SECTION 104.2.1 |
| | G) NO HORIZONTAL DRY VENTS AS SHOWN |
| | PAST ALL THE SHOWERS ON THE SECOND FLOOR |
| | ON THE RISER DIAGRAM. SECTION 905.3. |
| | 2) SEE RED LINE EXAMPLE OF A RISER |
| | DIAGRAM THAT REFLECTS THE FLOOR PLAN AND |
| | MEETS THE CODE REQUIREMENTS. |
| | 3) ALL DRAWING SHALL BEAR THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | THE DOCUMENT. SECTION 104.2.1 |
| | |
| | |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |