| 2004-11-17 00:00:00 | *********** UNSAT ***************** |
| | |
| | **PLANS NEED TO BE SUBMITTED FOR 2002 |
| | NEC CODE COMPLIANCE. |
| | PLEASE SEE THE FOLLOWING COMMENTS. |
| | |
| | 1)NOTE: PLEASE SUBMIT A COMPLETED RISER |
| | DIAGRAM TO MEET CODE COMPLIANCE. |
| | 215.5, 240.4,310.15B6/310.16, 240.4, |
| | 250.24, 250.122 ETC |
| | PLEASE SHOW A ON-LINE DIAGRAM FOR |
| | SERVICE AS IF LOOKING AT FRONT ELEVATION |
| | OF RISER. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | |
| | 3) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | |
| | 4)NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 5)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | TO MEET 220.31. |
| | PLEASE SEE LIGHTING LOAD FOR HOUSE, THIS |
| | DOES NOT CORRELATE WITH PLANS FOR SQ FT |
| | AND ALSO THE AMOUNT OF CIRCUITS NEEDED. |
| | SHOWS ALL 15A, #14. |
| | PLEASE SEE ALL CONTINUOUS LOADS (POOL |
| | PUMP, HEAT PUMP ARE TO BE SHOWN AT |
| | 125%. |
| | 230.42,215.3 ETC. |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52D IN MASTER BATH, YET AREA FOR |
| | ROMAN TUB SHOWS 7-GFI RECEPTS?? |
| | |
| | 8)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 9)NOTE: PLEAS LIST ARC FAULT PROTECTED |
| | CIRCUITS ON PANEL SCHEDULE. 210.12 2002 |
| | NEC. |
| | |
| | 10)NOTE: PLEASE SHOW LOCATION OF ALL |
| | SERVICE EQUIPMENT. PLANS ONLY SHOW PANEL |
| | IN STORAGE RM.215.5 |
| | |
| | 11)NOTE: PLEASE SEE 104.2.1 OF THE FBC |
| | FOR REQUIREMENTS OF PLANS. |
| | |
| | 12)NOTE: PLEASE SHOW ALL A/C EUIPMENT |
| | AND LOCATIONS OF THAT EQUIP. PLEASE |
| | INCLUDE DISCONNETS REQUIRED FOR THIS. |
| | 440.11 (COND UNITS). |
| | PLEASE SHOW ANNY POSSIBLE GFI'S REQUIRED |
| | FOR A/C EQUIPMENT. 210.63 |
| | |
| | 13)NOTE: PLEASE CORRELATE ALL A/C |
| | EQUIPMENT WITH MECHNICAL PLANS. |
| | PLEASE CORRELATE LOAD CALCULATIONS WITH |
| | MECH PLANS ALSO. 215.5 |
| | |
| | ** PLEASE SEE RECEPT SPACING ON PLANS, |
| | MOST RECEPT SPACING IS WAY ABOVE WHAT IS |
| | NEED FOR 210.52, THESE ARE PERMITTED |
| | YET SEEM TO BE MORE THAN NEEDED.** |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |