| 2004-12-14 00:00:00 | DENIED |
| | |
| | 1. 713.13 F.S.A NOTICE OF |
| | COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST |
| | BE |
| | RE-RECORDED IF THE DESCRIBED |
| | IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | 3. PRODUCT APPROVALS: |
| | MISSING FOR ROOFING AND FIXED GLASS. |
| | PLEASE SUBMIT 2 COPIES, WITH ATTACHED |
| | STATE APPROVAL. |
| | PC ALUMINUM DOOR HAS WRONG STATE |
| | APPROVAL ATTACHED. |
| | |
| | 4. C) PERMIT VALUATION HAS BEEN REVISED |
| | TO $650,000 AND ADDITIONAL PERMIT FEES |
| | OF $7162.56 ARE DUE. |
| | |
| | 5. SHOW DETAILS FOR THE FOLLOWING: |
| | |
| | |
| | 1015.2 HEIGHT. GUARDRAILS SHALL |
| | FORM A VERTICAL PROTECTIVE BARRIER NOT |
| | LESS THAN 42" HIGH. |
| | 1015.3 OPENINGS. OPEN GUARDRAILS |
| | SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| | MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| | SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| | RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| | REJECT THE PASSAGE OF 2" DIAMETER |
| | SPHERE. |
| | |
| | 6.SHOW ATTIC ACCESS SIZE AND LOCATION |
| | COMPLYING WITH FBC 2309.6 |
| | |
| | 7.SHOW ROOF DRAIN CALCULATIONS |
| | INCLUDING SCUPPER SIZE HEIGHT OF PARAPET |
| | WALL AND SQUARE FOOT AREA IN EACH DRAIN |
| | AREA. |
| | |
| | 9.ENERGY CALCS NOT SIGNED BY |
| | OWNER/AGENT. |
| | |
| | 10. SEE ELECTICAL NOTES #5 REGARDING |
| | SMOKE DETECTORS.FBC 905.2 |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |