| 2004-06-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT MEP-2 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. THE WASH | | | MACHINE SHALL NOT CONNECT UPSTREAM OF | | | THE LAUNDRY SINK AND TUB. SEE ATTACHED | | | SANT. RISER DIAGRAM TO SEE AN EXAMPLE OF | | | A RISER THAT MEETS CODE REQUIREMENTS. | | | SECTION 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|