| 2004-04-17 00:00:00 | *********** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE FS 471.219 FOR REQ'D |
| | CERTIFICATE OF AUTH # REQ'D. |
| | PLEASE SEE FAC 61G1-16.004 FOR ABOVE |
| | LICENSE # TO BE INCLUDED ON TITLE BLOCK. |
| | |
| | |
| | 2)NOTE: PLEASE SEE 104.1.1, PLEASE |
| | PROVIDE MORE INFORMATION IN CHANGE OF |
| | USE OR PORTION OF BLDG. |
| | PLANS APPEAR TO SHOW A NEW RESIDENCE |
| | BEING BUILT INTO THE SECOND FLOOR OF A |
| | COMMERCIAL BLDG? |
| | |
| | 3)NOTE: PLEASE SEE PLANS INDICATE OFCI |
| | IN LOCATIONS FOR GFCI. IS THIS THE SAME? |
| | STAIR LOCATION SEEMS TO SHOW WHAT APPEAR |
| | -S TO WALL SCONES WITH OFCI?? |
| | |
| | 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECTED. 210.8A6 |
| | |
| | 5)NOTE: PLEASE VERIFY REQ'D RECEPTS FOR |
| | BATHROOM(S) PER 210.52D, 210.11C3, AND |
| | GFCI PER 210.8 |
| | |
| | 6) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 7 )NOTE: PLEASE SEE MISSING REQ'D EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210.70 AND LS-101 5-8 |
| | HALLWAY LEADING INTO FOYER OF UNIT APPEA |
| | -RS TO SHOW MEANS OF EGRESS TO OUTSIDE |
| | AND ALSO FROM LAUNDRY ROOM. PLEASE |
| | CLARIFY IF THESE ARE GRADE LEVEL ACCESS? |
| | PLEASE ALSO CLARIFY NEW OR EXISTING |
| | BATHROOM LIGHTING? |
| | |
| | 8) NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | BEDROOM, WALL ARE LIVING RM |
| | |
| | 9)NOTE: PLEASE SEE 210.52H FOR MISSING |
| | HALLWAY RECEPT. |
| | |
| | 10)NOTE: PLEASE NOTE, WE ARE UNDER THE |
| | 2002 NEC AND ARC FAULT PROTECTION IS |
| | REQ'D FOR ALL BEDROOM OUTLETS. THIS IS |
| | INCLUDE SD'S. |
| | |
| | 11)NOTE: PLEASE CLARIFY SERVICE. SHOWS |
| | ONE METER, MAIN AND PANEL, YET THIS |
| | PANEL ONLY FEEDS WHAT APPEARS TO BE |
| | THIS RESIDENTIAL UNIT? |
| | RISER HAS A DIVISION LINE FOR BLDG EXT, |
| | AND APPEARS TO SHOW MAIN INSIDE? |
| | PLEASE SHOW LOCATION OF SERVICE/RISER |
| | ON PLANS. PLEASE ALSO VERIFY ADDITIONAL |
| | ELECTRICAL SERVICE. 230.2, 230.70, 230. |
| | 72 ETC. |
| | |
| | 12)NOTE: PLEASE SHOW LOCATION OF NEW |
| | COND UNIT, DISC AND RECEPT PER 440.11, |
| | 210.63. |
| | |
| | 13)NOTE: PLEASE SEE 424.3B FOR OCP OF |
| | AHU, HEAT. SHOWS 40A OCP FOR 10KW. |
| | |
| | 14)NOTE: PANEL SCHEDULE APPEARS TO SHOW |
| | ONLY ONE CIRCUIT FOR 3 BEDROOMS?? |
| | |
| | 15)NOTE: PLEASE SEE 210.52C2 FOR GFI |
| | RECEPT REQ'D FOR ISLAND. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |