| 2004-08-10 00:00:00 | DENIED: |
| | 1.PROVIDE ENERGY AND MANUAL J |
| | CALCULATIONS IN ACCORCANCE WITH THE |
| | 2001 FBC CHAPTER 13. |
| | |
| | 2.PROVIDE OUTSIDE AIR CALCUALTIONS |
| | FOR THE APARTMENTS BY NATURAL MEANS PER |
| | 2001 FBC(M) 402.2 & 402.2.1 OR 403.3. |
| | |
| | 3.PLAN SHEET M3.04, DETAIL INDICATES |
| | 6" DRYER EXHAUST AND 6" TOILET EXHAUST. |
| | DETAIL ALSO INDICATES A 6" & 4" IN |
| | SOFFIT AND APPEARS TO TERMINATE INTO A |
| | PLENUM BOX WITH A 12" X 8" WALL CAP. |
| | |
| | 4.PLEASE NOTE DRYER EXHAUST SHALL BE |
| | NON-SCREENED WITH A BACKDRAFT DAMPER |
| | AND THE TOILET EXHAUST TERMINATION SHALL |
| | BE SCREENED. 2001 FBC(M) 504.4 & 401.6, |
| | RESPECTIVELY. |
| | |
| | 5.PLEASE NOTE, EXHAUST DUCTS SHALL |
| | TERMINATE AS NOT TO CREATE A NUISANCE OR |
| | DIRECTED ONTO WALK-WAYS.2001 FBC(M) |
| | 401.5.2. |
| | |
| | 6.OUTSIDE AIR INTAKE AND EXHAUST SHALL |
| | BE LOCATED A MINIMUM OF 10 FT FROM LOT |
| | LINES OR BUILDINGS ON THE SAME LOT. |
| | INTAKE OPENINGS SHALL BE LOCATED A |
| | MINIMUM OF 10 FT FROM ANY NOXIOUS |
| | FUMES OR CONTAMINANT.2001 FBC(M) 401.5 |
| | AND 401.5.1. |
| | |
| | 7.PLAN SHEET M8.01, DETAIL FOR |
| | MOUNTING THE CONDENSOR UNIT.HEIGHT |
| | FROM THE ROOF SURFACE TO THE BOTTOM OF |
| | THE SUPPORT RAIL SHALL COMPLY WITH 2001 |
| | FBC 1511.7 |
| | |
| | 8.PLEASE PROVIDE DETAIL FOR CONDENSATE |
| | INDICATE TERMINATION.PROVIDE A MINIMUM |
| | OF 12" AWAY FROM THE BUILDING STRUCTURE |
| | AS PER 2001 FBC 1503.4.4. |
| | |
| | 9.SPECIFIC DRYERS INDICATED ON PLAN |
| | SHEET M8.01 SHALL BE INSTALLED FOR |
| | FINAL INSPECTION. |
| | |