| 2004-08-03 00:00:00 | ************** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE JURISDICTION NOTED |
| | ON PLANS. |
| | PROJECT IS UNDER THE CITY OF WEST PALM |
| | BEACH. |
| | |
| | 2)NOTE: PLEASE SEE CIRCUITING OF SD'S, |
| | SHOWN ON PANEL SCHEDULE AS BEING ON |
| | A CIRCUIT WHICH IS NOT ARC FAULT |
| | PROTECTED. PLEASE SEE 2002 NEC 210.12B |
| | WHICH REQUIRES ALL "OUTLETS" IN BEDRMS |
| | TO HAVE PROTECTION. FANS/LTS/SD'S/RECEPT |
| | |
| | 3)NOTE: PLEASE SEE PLANS ARE NOTED AS |
| | HAVING LV AND HV IN SAME RACEWAY TO |
| | ROOF FOR A/C EQUIPMENT.PLEASE PROVIDE |
| | NOTE PER 300.3C1 |
| | |
| | 4)NOTE: PLEASE CORRELATE RANGE LOADS, |
| | PANEL SCHEDULE INDICATES 7KW (8KW MIN |
| | PER NEC ) AND LOAD CALCS INDICATE 9KW? |
| | PLEASE CLARIFY. ARE THE RANGE UNIS |
| | PLEASE CLARIFY. ARE THE RANGE UNIS |
| | |
| | 5)NOTE:PLEASE SEE 210.52C1 FOR MISSING |
| | RECEPT ON 12" OF KITCHEN COUNTERSPACE. |
| | |
| | 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED. 210.8A6 |
| | |
| | 7)NOTE: PLEASE SEE UNIT #2 FOR SOME |
| | SPACING FOR RECEPTS PER 210.52 |
| | |
| | 8)NOTE: PLEASE CLARIFY:LOAD CALCS |
| | INDICATE TWO DIFFERENT TWO BEDROOM UNITS |
| | B&C, BUT ONLY ONE OF THE TWO BEDROOM |
| | UNIT LAYOUTS ARE SHOWN?? |
| | |
| | 9)NOTE: PLEASE SEE ALL MAINS MUST BE |
| | GROUPED PER 230.72. SHUNT TRIPS ARE NOT |
| | ACCEPTABLE BY THE CITY OF WEST PALM |
| | BEACH FOR GROUPING OF MAINS. |
| | SHUNT TRIPS ARE NOT RATED PER 230.76, |
| | 230.79. |
| | PLEASE PROVIDE MEANS OF DISC FOR 600A |
| | EQUIPMENT IN MAIN ELECTRICAL ROOM. |
| | |
| | EQUIPMENT IN MAIN ELECTRICAL ROOM. |
| | CLEARENCE REQUIRED OF EQUIPMENT ABOVE |
| | CLEARENCE REQUIRED OF EQUIPMENT ABOVE |
| | |
| | 11)NOTE: PLEASE PROVIDE NOTE ON ELEC- |
| | -TRICAL PLANS WHICH REFERENCEFHAR FOR |
| | DEVICES AND HEIGHTS. |
| | IT IS NOTED THAT THESE REQUIREMENTS ARE |
| | NOTED ON BLDG PLANS. |
| | |
| | 12)NOTE: |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 ETC. |
| | |
| | PLEASE SEE NOTES FROM OTHER REVIEWERS |
| | WHICH MAY OR MAY NOT HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | PLEASE SEE BLDG REVIEW COMMENTS FOR |
| | POSSIBLE TWO BLDG PERMITS? ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |