| 2004-04-06 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE FORM 600C OR ENERGY | | | & MANUAL J CALCULATIONS REQUIRED PER | | | 2001 FBC CHAPTER 13 SUB-SECTION 600.0 | | | METHOD A OR C. | | | | | | 2.PLAN INDICATES RETURN TRANSFER | | | GRILLES IN THE DOOR.PLEASE NOTE, PER | | | REVISED 2001 FBC(M) 601.4 EXCEPTION #2, | | | WHEN SIZING THROUGH THE WALL OR DOOR | | | TRANSFER GRILLES; SHALL USE 50 SQ INCHES | | | (OF GRILLE AREA) TO 100 CFM OF SUPPLY | | | AIR. | | | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3 OR 307.2.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|