Plan Review Notes
Plan Review Notes For Permit 04031701
Permit Number 04031701
Review Stop E
Sequence Number 3
Notes
Date Text
2004-08-18 00:00:00********** UNSAT 3RD REVIEW *********
  
 PLEASE SEE THE FOLLOWING NOTES FROM
 FIRST TWO REVIEWS STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE: NOTE #1 OK
  
 2)NOTE: NOTE #2 OK
  
 3)NOTE: NOTE #3 OK
  
 4)NOTE: NOTE #4 NO.
 PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 PLEASE SEE THIS IS STILL SHOWN ON W/
 GEN LTS AND RECEPTS,SD'S .
  
 5)NOTE: NOTE #5 OK
  
 6)NOTE: NOTE #6 NO.
 PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 SD'S STILL NOT SHOWN ON ARC FAULT PRO-
 -TECTED CIRCUITS.
  
 7)NOTE: NOTE #7 OK
  
 8)NOTE: NOTE #8 NO.
 PLEASE SEE A/C KW STILL SHOWN AS 4KW.
 PLEASE CORRELATE. ELECTRICAL PLANS WERE
 CORRECTED, HOWEVER A/C PLANS STILL SHOW
 4KW.
  
 9)NOTE: NOTE #9 OK
  
 10)NOTE: PLEASE SEE 250.58, REDLINE
 ITEM.
  
 11)NOTE: PLEASE SEE A NOTICE WAS GIVEN
 ON PREVIOUS REVIEW WITH RESPECT TO
 DESIGN PROFESSIONAL PER FS 553.80(2)(B)
 WHICH REQUIRES A 4X FEE FOR PLAN REVIEW
 PORTION OF PERMIT FEE FOR ANY OF THE
 SAME CODE COMPLIANCE NOT ADDRESSED THREE
 OR MORE TIMES.
 PLEASE SEE A 4X FEE FOR PLAN REVIEW HAS
 NOW BEEN ACCESSED.
 PLEASE SEE BZ#245127 $960.00 ATTACHED TO
 PLANS. THIS IS REQUIRED UNDER STATE LAW
 AND MUST BE PAID ALONG WITH RESUB FEE
 BEFORE SUBMITTING PLANS FOR REVIEW.
 PLEASE SEE ONE SET OF ELECTRICAL SHEETS
 FROM EACH SUBMITTAL HAS NOW BEEN RETAIN-
 -ED FOR FILE. PLANS AT THIS TIME MAY BE
 FILED FOR REVIEW BY STATE BOARD OF ARCH.
 **PLEASE SEE AS OF TODAY'S DATE, NO
 ONE HAS CONTACTED MYSELF TO GO OVER
 COMMENTS. NAME, PHONE # AND E-MAIL
 ADDRESS HAS BEEN AT THE BOTTOM OF EACH
 REVIEW NOTES.** PLEASE DO NOT HESITATE
 IN CONTACTING ME IF THERE ARE ANY
 QUESTIONS.
  
  
 **PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]