| 2004-08-18 00:00:00 | ********** UNSAT 3RD REVIEW ********* |
| | |
| | PLEASE SEE THE FOLLOWING NOTES FROM |
| | FIRST TWO REVIEWS STILL NEED TO BE |
| | ADDRESSED. |
| | |
| | 1)NOTE: NOTE #1 OK |
| | |
| | 2)NOTE: NOTE #2 OK |
| | |
| | 3)NOTE: NOTE #3 OK |
| | |
| | 4)NOTE: NOTE #4 NO. |
| | PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | PLEASE SEE THIS IS STILL SHOWN ON W/ |
| | GEN LTS AND RECEPTS,SD'S . |
| | |
| | 5)NOTE: NOTE #5 OK |
| | |
| | 6)NOTE: NOTE #6 NO. |
| | PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | SD'S STILL NOT SHOWN ON ARC FAULT PRO- |
| | -TECTED CIRCUITS. |
| | |
| | 7)NOTE: NOTE #7 OK |
| | |
| | 8)NOTE: NOTE #8 NO. |
| | PLEASE SEE A/C KW STILL SHOWN AS 4KW. |
| | PLEASE CORRELATE. ELECTRICAL PLANS WERE |
| | CORRECTED, HOWEVER A/C PLANS STILL SHOW |
| | 4KW. |
| | |
| | 9)NOTE: NOTE #9 OK |
| | |
| | 10)NOTE: PLEASE SEE 250.58, REDLINE |
| | ITEM. |
| | |
| | 11)NOTE: PLEASE SEE A NOTICE WAS GIVEN |
| | ON PREVIOUS REVIEW WITH RESPECT TO |
| | DESIGN PROFESSIONAL PER FS 553.80(2)(B) |
| | WHICH REQUIRES A 4X FEE FOR PLAN REVIEW |
| | PORTION OF PERMIT FEE FOR ANY OF THE |
| | SAME CODE COMPLIANCE NOT ADDRESSED THREE |
| | OR MORE TIMES. |
| | PLEASE SEE A 4X FEE FOR PLAN REVIEW HAS |
| | NOW BEEN ACCESSED. |
| | PLEASE SEE BZ#245127 $960.00 ATTACHED TO |
| | PLANS. THIS IS REQUIRED UNDER STATE LAW |
| | AND MUST BE PAID ALONG WITH RESUB FEE |
| | BEFORE SUBMITTING PLANS FOR REVIEW. |
| | PLEASE SEE ONE SET OF ELECTRICAL SHEETS |
| | FROM EACH SUBMITTAL HAS NOW BEEN RETAIN- |
| | -ED FOR FILE. PLANS AT THIS TIME MAY BE |
| | FILED FOR REVIEW BY STATE BOARD OF ARCH. |
| | **PLEASE SEE AS OF TODAY'S DATE, NO |
| | ONE HAS CONTACTED MYSELF TO GO OVER |
| | COMMENTS. NAME, PHONE # AND E-MAIL |
| | ADDRESS HAS BEEN AT THE BOTTOM OF EACH |
| | REVIEW NOTES.** PLEASE DO NOT HESITATE |
| | IN CONTACTING ME IF THERE ARE ANY |
| | QUESTIONS. |
| | |
| | |
| | **PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |