Plan Review Notes
Plan Review Notes For Permit 04031701
Permit Number 04031701
Review Stop E
Sequence Number 2
Notes
Date Text
2004-06-04 00:00:00********* UNSAT ***********
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 WERE NOT ADDRESSED.
  
 NOTE #1 NO. GROUPING OF MAINS NOT SHOWN
 PLEASE SEE CONDUCTORS ARE STILL SHOWN
 OVERSIZED BUT PERMITTED.
 PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN DISC TO PANEL.
 250.110,250.24, SIZE PER 250.122
  
 NOTE #2 OK
  
 NOTE #3 SM APPL CIRCUITS ADDED, HOWEVER
 WRONG LOAD IS SHOWN PER 220.16.
  
 NOTE #4 NO
  
 NOTE #5 OK
  
 NOTE #6 NO
  
 NOTE #7 OK
  
 NOTE #8 ?? 4KW STILL SHOWN FOR HEAT LOAD
 ?
 NOTE #9 OK
  
 NEW NOTE:
 1)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) THIS IS GIVEN AS A
 NOTICE AFTER SECOND REVIEW W/ ANY OF THE
 SAME COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]