| Plan Review Notes For Permit 04031701 |
| Permit Number |
04031701 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-06-04 00:00:00 | ********* UNSAT *********** | | | | | | PLEASE SEE SOME NOTES FROM FIRST REVIEW | | | WERE NOT ADDRESSED. | | | | | | NOTE #1 NO. GROUPING OF MAINS NOT SHOWN | | | PLEASE SEE CONDUCTORS ARE STILL SHOWN | | | OVERSIZED BUT PERMITTED. | | | PLEASE SEE MISSING EQUIPMENT GROUNDING | | | CONDUCTOR FROM MAIN DISC TO PANEL. | | | 250.110,250.24, SIZE PER 250.122 | | | | | | NOTE #2 OK | | | | | | NOTE #3 SM APPL CIRCUITS ADDED, HOWEVER | | | WRONG LOAD IS SHOWN PER 220.16. | | | | | | NOTE #4 NO | | | | | | NOTE #5 OK | | | | | | NOTE #6 NO | | | | | | NOTE #7 OK | | | | | | NOTE #8 ?? 4KW STILL SHOWN FOR HEAT LOAD | | | ? | | | NOTE #9 OK | | | | | | NEW NOTE: | | | 1)NOTE: PLEASE SEE ATTACHED COPY OF | | | FS 553.80(2)(B) THIS IS GIVEN AS A | | | NOTICE AFTER SECOND REVIEW W/ ANY OF THE | | | SAME COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|