Plan Review Notes
Plan Review Notes For Permit 04031701
Permit Number 04031701
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-16 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE CLARIFY SERVICE SHOWN??
 SHOWS NEW 100A METERCAN WITH 500MCM
 FEEDING CAN? ALSO SHOWS NEW 3/0'S FEED-
 -ING 100A DISC. PLEASE VERIFY SIZE OF
 LUGS. LARGER CONDUCTORS MAY BE USED
 BUT SEEMED TO BE OVERSIZED FOR 100A SERV
 ICE?
 PLEASE VERIFY GROUPING OF MAINS FOR
 BLDG. 230.72. ETC.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE SEE 210.11C1 FOR A MIN
 OF TWO SM APPL CIRCUITS REQ'D. 220.16
 ONE SHOWN.
  
 4)NOTE: PLEASE SEE210.11C3 FOR MIN
 REQ'D FOR BATH. THIS IS NOT ON W/ GEN
 LT ANS RECEPTS AS INDICATED.
  
 5)NOTE: PLEASE SEE PLANS REFERENCE THE
 1999 NEC. THE STATE ADOPTED THE 2002 NEC
 JULY 1ST, 2003
  
 6)NOTE: PLEASE SEE 210.12 FOR ARC FAULT
 PROTECTION REQ'D. SD'S ARE SHOWN ON
 BATH/LTS W/OUT AFCI.
  
 7)NOTE: PLEASE SEE MISSING RECEPT FOR
 2' OF WALL PER 210.52 BDRM#2
  
 8)NOTE: PLEASE CHECK KW RATING SHOWN
 FOR AHU HEAT. 4KW IS NOT A COMMON SIZE.
  
 9)NOTE: PLEASE SHOW DISC MEANS FOR A/C
 COND UNIT. 440.11
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]