| 2004-04-16 00:00:00 | ************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE CLARIFY SERVICE SHOWN?? |
| | SHOWS NEW 100A METERCAN WITH 500MCM |
| | FEEDING CAN? ALSO SHOWS NEW 3/0'S FEED- |
| | -ING 100A DISC. PLEASE VERIFY SIZE OF |
| | LUGS. LARGER CONDUCTORS MAY BE USED |
| | BUT SEEMED TO BE OVERSIZED FOR 100A SERV |
| | ICE? |
| | PLEASE VERIFY GROUPING OF MAINS FOR |
| | BLDG. 230.72. ETC. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3)NOTE: PLEASE SEE 210.11C1 FOR A MIN |
| | OF TWO SM APPL CIRCUITS REQ'D. 220.16 |
| | ONE SHOWN. |
| | |
| | 4)NOTE: PLEASE SEE210.11C3 FOR MIN |
| | REQ'D FOR BATH. THIS IS NOT ON W/ GEN |
| | LT ANS RECEPTS AS INDICATED. |
| | |
| | 5)NOTE: PLEASE SEE PLANS REFERENCE THE |
| | 1999 NEC. THE STATE ADOPTED THE 2002 NEC |
| | JULY 1ST, 2003 |
| | |
| | 6)NOTE: PLEASE SEE 210.12 FOR ARC FAULT |
| | PROTECTION REQ'D. SD'S ARE SHOWN ON |
| | BATH/LTS W/OUT AFCI. |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPT FOR |
| | 2' OF WALL PER 210.52 BDRM#2 |
| | |
| | 8)NOTE: PLEASE CHECK KW RATING SHOWN |
| | FOR AHU HEAT. 4KW IS NOT A COMMON SIZE. |
| | |
| | 9)NOTE: PLEASE SHOW DISC MEANS FOR A/C |
| | COND UNIT. 440.11 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |