| 2004-04-28 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04031701 |
| | ADD: 633 10TH ST |
| | CONT: RICHARD BUEU |
| | TEL: (754)422-6896 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) THE PRIMARY ENTRY DOOR OF COVERED |
| | DWELLING UNITS IS PART OF PUBLIC AND |
| | COMMON USE SPACES, THEREFORE, IT MUST BE |
| | ON AN ACCESSIBLE ROUTE & BE ACCESSIBLE, |
| | I.E., MEET THE ANSI REQUIREMENTS OF |
| | 4.13 DOORS. ANSI 4.13.9 LEVER OR OTHER |
| | EASY USE DOOR HARDWARE. |
| | |
| | 3) PRIMARY ENTRY DOORS TO COVERED |
| | UNITS MUST BE ON AN ACCESSIBLE ROUTE, |
| | THRESHOLDS AT THESE DOORS MUST BE NO |
| | HIGHER THAN 3/4" AND MUST BE BEVELED |
| | WITH A SLOPE NO GREATER THAN 1:2. |
| | |
| | 4)FBC 13-103.1.2 BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | |
| | 5)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 6) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | PROVIDE LOCAL PRODUCT APPROVAL FOR |
| | THE RAISED WOOD DOOR FROM FLORIDA LUMBER |
| | COMPANY. NOT LISTED ON THE STATE PRODUCT |
| | APPROVAL SYSTEM OR SUBMIT A DIFFERENT |
| | APPROVED PRODUCT. |
| | |
| | 7) THE SINGLE HUNG WINDOW SUBMITTED FROM |
| | PGT, INDICATE WHICH GLASS STRENGTH THAT |
| | WILL BE USED, 3/16" DSB OR SSB, THE |
| | ALLOWABLE PRESSURES VERY UPON THE |
| | STRENGTH OF GLAZING USED. |
| | |
| | 8) 1707.4.4.2 TAPERED BUCKS: |
| | SHALL EXTEND BEYOND THE INTERIOR FACE |
| | OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |