2004-04-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04031701
 ADD: 633 10TH ST
 CONT: RICHARD BUEU
 TEL: (754)422-6896
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE PRIMARY ENTRY DOOR OF COVERED
 DWELLING UNITS IS PART OF PUBLIC AND
 COMMON USE SPACES, THEREFORE, IT MUST BE
 ON AN ACCESSIBLE ROUTE & BE ACCESSIBLE,
 I.E., MEET THE ANSI REQUIREMENTS OF
 4.13 DOORS. ANSI 4.13.9 LEVER OR OTHER
 EASY USE DOOR HARDWARE.
  
 3) PRIMARY ENTRY DOORS TO COVERED
 UNITS MUST BE ON AN ACCESSIBLE ROUTE,
 THRESHOLDS AT THESE DOORS MUST BE NO
 HIGHER THAN 3/4" AND MUST BE BEVELED
 WITH A SLOPE NO GREATER THAN 1:2.
  
 4)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 5)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 6) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 PROVIDE LOCAL PRODUCT APPROVAL FOR
 THE RAISED WOOD DOOR FROM FLORIDA LUMBER
 COMPANY. NOT LISTED ON THE STATE PRODUCT
 APPROVAL SYSTEM OR SUBMIT A DIFFERENT
 APPROVED PRODUCT.
  
 7) THE SINGLE HUNG WINDOW SUBMITTED FROM
 PGT, INDICATE WHICH GLASS STRENGTH THAT
 WILL BE USED, 3/16" DSB OR SSB, THE
 ALLOWABLE PRESSURES VERY UPON THE
 STRENGTH OF GLAZING USED.
  
 8) 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026