2007-02-07 14:58:09REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT P4.01 SANITARY RISER DIAGRAM. (REVISION 6), 6"
 HUB DRAIN NOT VENTED. SECTION 901.2.1. PLEASE INDICATED
 WHICH FLOOR THE 6" HUB DRAIN WILL BE LOCATED ON.--
 6" HUB DRAIN ON THE FIRST FLOOR INDICATES AN AAV VENT.
 THIS AAV VENT REQUIRES A RELIEF VENT PER SECTION
 917.3.2.--THE HORIZONTAL BLDG SANITARY DRAIN
 DOWNSTREAM OF RISER "G" IS INDICATED AS A 4" DRAIN.
 RISER "G" IS INDICATED AS 6". PER SECTION 704.2 THE
 SIZE OF THE DRAINAGE PIPE SHALL NOT BE REDUCED IN THE
 DIRECTION OF FLOW. SHOW ALL DFU'S AS THEY ACCUMULATE IN
 THE SYSTEM IN ALL REVISED DRAINAGE PIPING. TABLES
 710.1(1) & 710.1(2).-- THE 6" BUILDING DRAIN
 DOWNSTREAM OF WHERE THE BRANCH LINE TO RISER "G"
 CONNECTS TO THE BUILDING DRAIN IS INDICATED AS 6".
 AFTER ALL DFU'S ARE ADDED UP, (MAXIMUM 700 DFU@6"),I
 BELIEVE 8" WILL BE REQUIRED.--ADJUST ALL
 ACCUMULATED DFU'S DOWNSTREAM OF BOTH THE NEW 6" HUB
 DRAINS TO THE BUILDING SEWER CONNECTION.
  
 REVIEW BY KEN STEVENS