| Plan Review Notes For Permit 04031591 |
| Permit Number |
04031591 |
|
| Review Stop |
P |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2007-02-07 14:58:09 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1. SHT P4.01 SANITARY RISER DIAGRAM. (REVISION 6), 6" | | | HUB DRAIN NOT VENTED. SECTION 901.2.1. PLEASE INDICATED | | | WHICH FLOOR THE 6" HUB DRAIN WILL BE LOCATED ON.-- | | | 6" HUB DRAIN ON THE FIRST FLOOR INDICATES AN AAV VENT. | | | THIS AAV VENT REQUIRES A RELIEF VENT PER SECTION | | | 917.3.2.--THE HORIZONTAL BLDG SANITARY DRAIN | | | DOWNSTREAM OF RISER "G" IS INDICATED AS A 4" DRAIN. | | | RISER "G" IS INDICATED AS 6". PER SECTION 704.2 THE | | | SIZE OF THE DRAINAGE PIPE SHALL NOT BE REDUCED IN THE | | | DIRECTION OF FLOW. SHOW ALL DFU'S AS THEY ACCUMULATE IN | | | THE SYSTEM IN ALL REVISED DRAINAGE PIPING. TABLES | | | 710.1(1) & 710.1(2).-- THE 6" BUILDING DRAIN | | | DOWNSTREAM OF WHERE THE BRANCH LINE TO RISER "G" | | | CONNECTS TO THE BUILDING DRAIN IS INDICATED AS 6". | | | AFTER ALL DFU'S ARE ADDED UP, (MAXIMUM 700 DFU@6"),I | | | BELIEVE 8" WILL BE REQUIRED.--ADJUST ALL | | | ACCUMULATED DFU'S DOWNSTREAM OF BOTH THE NEW 6" HUB | | | DRAINS TO THE BUILDING SEWER CONNECTION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|