Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop E
Sequence Number 6
Notes
Date Text
2005-08-10 00:00:00**********UNSAT *********
  
 REVS' #5 AND 6
  
 1)NOTE: PLEASE SEE RECEPTS MISSING FOR
 2' OF WALL SPACE IN KITCHENS IN SOME
 UNITS. 210.52
 THESE WERE REDLINED ON ONE SET OF PLANS.
 B-9,B-2, PH-8,,
  
 2)NOTE: PLEASE SEE PH-8 MENTIONS 2BDRM/
 2BATH, HOWEVER PLANS INDICATE 3 BEDRMS?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE SD OUTSIDE BEDRM IN
 PH-9.
 PLEASE ALSO SEE UNITS WITH SD'S SHOWN IN
 AREA WHICH APPEAR TO HAVE A "LOWERED
 CEILING". PLEASE BE SURE ALL SD'S ARE
 INSTALLED WITH IN 3' OF A PEAK AND W/IN
 18" OF CEILING.
 NFPA-72 CHAPTER 2
  
 4)NOTE: PLEASE SEE A "PROVISO" WAS GIVEN
 IN ORDER FOR BLDG PERMIT TO BE ISSUED.
 PLEASE SEE THIS "PROVISO" GIVEN REQUIRE
 DTHE GENERATOR, ATS, FIRE PUMP AND FIRE
 PUMP CONTROLLER TO BE UNDER SEPARATE
 PERMIT.
 AS OF TODAY'S DATE , NO PERMIT
 APPLICATION HAS BEEN SUBMITTED FOR THE
 ABOVE ITEMS.
 GEN AND ATS SAHLL BE SEAPARATE FROM FIRE
 PUMP AND FIRE PUMP CONTROLLER PERMIT.
 PLEASE UNDERSTAND NO OTHER ELECTRICAL
 REV'S WILL BE PASSED UNTIL "PROVISO" IS
 ADDRESSED.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]