| 2005-07-15 00:00:00 | ARCHITECTURAL AND STRUCTURAL REVISION |
| | SUBMITTED 5/4/05 FOR GENERAL UPDATE OF |
| | PLANS. |
| | |
| | ONLY THE FOLLOWING SHEETS NEED TO BE |
| | REVISED AND RE-SUBMITTED.ALL OTHER |
| | SHEETS HAVE BEEN STAMPED AND ONE COPY |
| | RETAINED FOR RECORDS: |
| | |
| | 1) FBC 704.1SHEET A0-3, GROUND LEVEL |
| | LIFE SAFETY PLAN.OCCUPANCY OF THE |
| | RELOCATED VALET STATION IS NOT LABELLED. |
| | THE LABEL 'VALET' SHOULD BE MOVED FROM |
| | THE OLD LOCATION TO THE NEW SO THAT |
| | OCCUPANCY SEPARATION CAN BE CONFIRMED |
| | UNNECESSARY. |
| | |
| | 2) SHEET A0-3 AND A1-1THE NEW EGRESS |
| | DOOR ADJACENT THE RELOCATED VALET |
| | STATION SWINGS ACROSS THE CURB INTO THE |
| | PARKING GARAGE VEHICLE ACCESSWAY.THE |
| | DOOR COULD BE STRUCK BY AN EXITTING |
| | VEHICLE AND CAUSE PERSONAL INJURY TO |
| | PERSONS USING THE DOOR.AMEND THE PLAN. |
| | |
| | 3) SHEET A8-1TO EXPEDITE PERMIT ISSUE, |
| | EACH COPY OF THIS SHEET IN THE PERMITTED |
| | SET OF PLANS INCLUDED A HANDRITTEN NOTE: |
| | "PRE-CAST MOULDINGS SHALL BE |
| | MECHANICALLY FASTENED TO STRUCTURE, |
| | MANUFACTURER TO SUBMIT SHOP DRAWINGS FOR |
| | APPROVAL"-SIGNED AND DATED BY STUART |
| | COHEN.THIS NOTE MUST BE ADDED TO THE |
| | REVISED SHEET A8-1 BEFORE IT IS PRINTED, |
| | SIGNED AND SEALED. |
| | |
| | 4) SHEET A9-1TO EXPEDITE PERMIT ISSUE, |
| | INTERIOR ELEVATIONS 1 TO 6 ON EACH COPY |
| | OF THIS SHEET, IN THE PERMITTED SET OF |
| | PLANS, WERE REDLINED TO SHOW THE |
| | REQUIRED HEIGHTS FOR THE VANITY (2'-10" |
| | AFFL) AND THE W.C. (BETWEEN 17" AND 19" |
| | AFFL). THESE DIMENSIONS MUST BE ADDED TO |
| | THE REVISED SHEET A9-1 BEFORE IT IS |
| | PRINTED, SIGNED AND SEALED. |
| | |
| | 5) SHEETS A4-0, A4-1 AND A4-2NORTH, |
| | EAST AND SOUTH ELEVATIONS.SUBMIT |
| | DETAILS TO SHOW THE LEVEL TRANSITION |
| | (STEPS/RAMPS), AT EACH ENTRY WAY, FROM |
| | THE SIDEWALK TO THE (NOW RAISED) GROUND |
| | FLOOR SLAB.IF NO TRANSITION IS |
| | REQUIRED, THEN THIS SHOULD BE JUSTIFIED |
| | BY AMENDING THE ELEVATIONS TO CLARIFY |
| | THE RELATIONSHIP BETWEEN SIDEWALK LEVEL |
| | PROFILE AND GROUND FLOOR SLAB LEVELS. |
| | |
| | 6) THE PROVISOS ATTACHED TO THE |
| | PERMITTED SET OF PLANS HAVE NOT YET BEEN |
| | ADDRESSED.A COPY IS ATTACHED TO THESE |
| | NOTES.PLEASE ADDRESS THE PROVISOS OR |
| | PROVIDE A LETTER GIVING THE TIME-FRAME |
| | IN WHICH THEY WILL BE ADDRESSED. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |