| Date |
Text |
| 2008-01-23 16:57:13 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | NOTE: IN ORDER TO EXPIDITE THE GAS REVISION FOR THE |
| | BUILDING C/O, CHIEF PLUMBING INSPECTOR LARRY WAGNER |
| | FIELD INSPECTED ALL GAS APPLIANCES TO VERIFY BTU LOAD |
| | ON THE APPLIANCE NAME PLATES AND ALSO TO VERIFY THE MP |
| | REGULATORS MAKE AND MODEL NUMBER INSTALLED PER THE |
| | APPLIANCES. THOSE COMMENTS WILL FOLLOW THE PREVIOUS |
| | PLAN REVIEW COMMENTS AS NEW COMMENTS: |
| | |
| | **PREVIOUS PLAN REVIEW COMMENTS** |
| | |
| | 1. **NO COMMENT RESPONSE, COMMENT NOT ADDRESSED** |
| | SHEET P4.16: SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY |
| | SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION *401.1 SCOPE. |
| | ***THE RESUBMITTED REVISION STILL ARE NOT CLEARLY |
| | INDICATING THE CORRESPONDING LENGTHS TO ALL CUT |
| | SECTIONS OF PIPE. PLESE REFERENCE THE RED CIRCLED AREA |
| | AND YELLOW HIGH LIGHTED PIPES WITH NO CORRESPONDING |
| | LENGTHS. |
| | |
| | 2. **OK** COMMENT ADDRESSED. |
| | |
| | 3. **OK** COMMENT ADDRESSED. |
| | |
| | 4. **NO COMMENT RESPONSE, COMMENT NOT ADDRESSED** |
| | SHEET P4.16: PLEASE CORRELATE THE LONGEST RUN PER |
| | COMMENT #1. |
| | NOTE: UNTIL COMMENT #1 IS PROPERLY ADDRESSED THIS |
| | COMMENT WILL CONTINUE TO APPEAR. |
| | |
| | **NEW COMMENTS PER FIELD INSPECTION AND APPLIANCE |
| | SUBMITTALS** |
| | |
| | 5. AT A MINIMUM THE REVISED PLANS SHALL REFLECT WHAT |
| | IS INSTALLED AND THEY DO NOT. PLEASE CORRECT THE PLANS |
| | TO REFLECT THE FOLLOWING ON ALL AREAS OF THE PLAN |
| | SHEET. PER FBC FUEL GAS SECTION *401.1, SCOPE. |
| | |
| | "APPLIANCE LOAD TABLE" |
| | |
| | A- POOL/SPA HEATER (2) @300 CFH (EA.) TOTAL BTU'S = |
| | 600,000 OR 600 CFH. |
| | |
| | B- BOILER = 1,480,000 BTU'S OR 1480 CFH. |
| | |
| | C- WATER HEATER = 1,050,000 BTU'S OR 1050 CFH. |
| | |
| | D- WATER HEATER = 1,050,000 BTU'S OR 1050 CFH. |
| | |
| | NOTE: PER MAXITROL ([email protected]) THE 325-7 IS |
| | ONLY RATED FOR 900,000 BTU'S. THE 325-7 WOULD NEED A |
| | MINIMUM OF 1 PSI ON THE INLET AND THE 210 CAN WORK AT |
| | 14" W.C.PRESSURE. THE 210 SERIES IS NOT A DEAD END LOCK |
| | UP. |
| | |
| | **WITH THE FACTS BEING STATED FROM MAXITROL NEITHER |
| | REGULATOR IS ACCEPTABLE DUE TO THE PRESSURE LOSS OF THE |
| | SYSTEM (42.024 WATER COL. PRESSURE DROP OF SYSTEM WHICH |
| | LEAVES LESS THAN 0.5 PSI AT THE REGULATORS), LOAD |
| | CAPACITY OF REGULATORS (325-7 RATED 900,000 BTU), AND |
| | 210 SERIES NOT BEING A DEAD END LOCK UP, WHICH MEANS |
| | UNDER STATIC CONDITIONS WHEN NO GAS IS FLOWING, OUTLET |
| | PRESSURE WILL RISE TO LINE PRESSURE. |
| | |
| | **IT IS SUGGESTED THAT SYSTEM DELIVERY PRESSURE BE |
| | INCREASE TO 5 PSI AND THE PROPER MP REGULATORS BE |
| | INSTALLED AFTER CONFERRING WITH THE MANUFACTURER. THREE |
| | COPIES OF THE MP REGULATOR MANUFACTURER'S SPECIFICATION |
| | SHEETS WITH THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY, |
| | AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY ARE REQUIRED. |
| | |
| | 6. SHEET P4.16 KEY NOTES: #11 IS INDICATING THE WRONG |
| | WATER HEATER MAKE PER THE SUBMITTAL. THE CORRECT WATER |
| | HEATER MAKE IS "RBI LCD 1050" @ 1,050,000 BTU'S. |
| | |
| | 7. SHEET P4.16 KEY NOTES: #12 IS INDICATING THE WRONG |
| | BOILER MAKE PER THE SUBMITTALS. THE CORRECT BOILER MAKE |
| | IS "RBI LCD 1480 @ 1,480,000 BTU'S. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |