| Plan Review Notes For Permit 04031591 |
| Permit Number |
04031591 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-11-09 00:00:00 | PROVISO: | | | | | | 1.PLAN SHEET M6.04, NOTE INDICATES | | | "DRYER SHALL BE INCAPACITATED IF | | | BOOSTER FAN FAILS".ELECTRICAL PLANS DO | | | NOT SPECIFY THIS CONDITION. | | | | | | PLEASE PROVIDE SUBMITTAL SHOWING THE | | | CONTROL CIRCUIT INDICATING DRYER FEED | | | BEING OPENED ON FAN FAILURE, | | | (AUXILIARY CONTACT). | | | | | | 2.PLEASE NOTE, PLAN SHEET M8.01 | | | INDICATES THE GARAGE EXHAUST SYSTEM &CO | | | SENSORS SHALL BE CONNECTED TO THE | | | EMERGENCY POWER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @ (561)805-6719. |
|