Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop G
Sequence Number 4
Notes
Date Text
2008-01-14 13:14:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 REVISION DENIED:
  
 1. SHEET P4.16: SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION *401.1 SCOPE. **THE RESUBMITTED
 PLANS STILL ARE NOT CLEARLY INDICATING THE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 PLEASE REFERENCE THE RED CIRCLED AREA AND YELLOW HIGH
 LIGHTED PIPES WITH NO CORRESPONDING LENGTHS.
  
 2. SHEET P4.16: PER FBC-2004 FUEL GAS, SECTION *409.4
 MP REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 **RESUBMITTED PLANS ARE NOT INDICATING THESE REQUIRED
 VALVES. NOTE: THE INDICATED MANIFOLD VALVE IS NOT
 ACCEPTABLE FOR THIS AND SHOULD BE DELETED.
  
 3. SHEET P4.16: THE 3" COPPER VENT UP THRU ROOF OFF
 THE 2" GAS SUPPLY PIPE MAKES NO SENSE. THE 2 PSI GAS
 PRESSURE WILL BE LOST THROUGH THIS DESIGN. PLEASE
 CORRECT THIS ON THE RESUBMITTAL. PER SECTION *401.1,
 SCOPE.
  
 4. SHEET P4.16: PLEASE CORRELATE THE LONGEST RUN PER
 COMMENT #1. **THE ADDED SUM OF THE INDICATED
 CORRESPONDING LENGTHS OF CUT SECTIONS OF PIPE ON THIS
 REVISION SUBMITTAL IS 472'-7", THE INDICATED LONGEST
 RUN ON THE PLANS IS NOW 470'-0". UNTIL COMMENT #1 IS
 PROPERLY ADDRESSED THIS FIGURE WILL AGAIN BE WRONG.
 NOTE: THE RESUBMITTED PLANS WITH THE CALCULATION "
 MAXIMUM ALLOWABLE PRESSURE DROP 1.5 PSI (42" W.C.)
 AGAIN IS WRONG PER THE ADDED SUM OF THE 1ST SECTION OF
 PIPE WHICH IS NOW 269'-7". HOWEVER UNTIL PLANS ARE
 COMPLETELY CORRELATED THIS TABLE WILL CONTINUE TO BE
 WRONG. PER SECTION *401.1, SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL/REVISION REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved