| Date |
Text |
| 2008-01-14 13:14:09 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | 1. SHEET P4.16: SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION *401.1 SCOPE. **THE RESUBMITTED |
| | PLANS STILL ARE NOT CLEARLY INDICATING THE |
| | CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. |
| | PLEASE REFERENCE THE RED CIRCLED AREA AND YELLOW HIGH |
| | LIGHTED PIPES WITH NO CORRESPONDING LENGTHS. |
| | |
| | 2. SHEET P4.16: PER FBC-2004 FUEL GAS, SECTION *409.4 |
| | MP REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE |
| | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| | **RESUBMITTED PLANS ARE NOT INDICATING THESE REQUIRED |
| | VALVES. NOTE: THE INDICATED MANIFOLD VALVE IS NOT |
| | ACCEPTABLE FOR THIS AND SHOULD BE DELETED. |
| | |
| | 3. SHEET P4.16: THE 3" COPPER VENT UP THRU ROOF OFF |
| | THE 2" GAS SUPPLY PIPE MAKES NO SENSE. THE 2 PSI GAS |
| | PRESSURE WILL BE LOST THROUGH THIS DESIGN. PLEASE |
| | CORRECT THIS ON THE RESUBMITTAL. PER SECTION *401.1, |
| | SCOPE. |
| | |
| | 4. SHEET P4.16: PLEASE CORRELATE THE LONGEST RUN PER |
| | COMMENT #1. **THE ADDED SUM OF THE INDICATED |
| | CORRESPONDING LENGTHS OF CUT SECTIONS OF PIPE ON THIS |
| | REVISION SUBMITTAL IS 472'-7", THE INDICATED LONGEST |
| | RUN ON THE PLANS IS NOW 470'-0". UNTIL COMMENT #1 IS |
| | PROPERLY ADDRESSED THIS FIGURE WILL AGAIN BE WRONG. |
| | NOTE: THE RESUBMITTED PLANS WITH THE CALCULATION " |
| | MAXIMUM ALLOWABLE PRESSURE DROP 1.5 PSI (42" W.C.) |
| | AGAIN IS WRONG PER THE ADDED SUM OF THE 1ST SECTION OF |
| | PIPE WHICH IS NOW 269'-7". HOWEVER UNTIL PLANS ARE |
| | COMPLETELY CORRELATED THIS TABLE WILL CONTINUE TO BE |
| | WRONG. PER SECTION *401.1, SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL/REVISION REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |